Plan Review Notes
Plan Review Notes For Permit 07060772
Permit Number 07060772
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-06 10:13:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ADDRESSED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 2ND REVIEW, ENGINEER REQUESTED CLARIFICATION.PLEASE
 FIND THE FLORIDA STATE PRODUCT APPROVAL FOR EACH NOA.
 THIS CAN BE DONE BY SEARCHING BY MANUFACTURER AT THE
 WEBSITE REFERENCED, WWW.FLORIDABUILDING.ORG.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL CAN BE ISSUED FOR
 FBC COMPLIANT PRODUCTS USING THE NOA.THE REVIEW FOR
 LOCAL PRODUCT APPROVAL WILL BE DONE IF IT IS DETERMINED
 THAT A FLORIDA STATE PRODUCT APPROVAL HAS NOT BEEN
 ISSUED.
  
 3.)GOVERNING CODE IS TO INCLUDE 2005 AND 2006
 AMENDMENTS.
  
 2ND REVIEW, PLANS WERE CHANGED SO THAT THE STAIR NOTES
 REFER TO 2005 AND 2006 LOCAL AMENDMENTS.THE REQUEST
 IS TO ESTABLISH GOVERNING CODE ON THE PLAN BASED ON
 APPLICATION DATE.2006 AMENDMENTS ARE APPLICABLE IN
 THIS CASE.THESE ARE NOT LOCAL AMENDMENTS; THEY ARE
 AMENDMENTS TO THE FLORIDA BUILDING CODE 2004 AT THE
 STATE LEVEL.
  
 4.)N/A
  
 5-10)ADDRESSED.
  
 11.)A1, THE ROOF IS A FLAT DECK WITH NO PARAPET WALL
 SHOWN; PROVIDE CALCULATIONS FOR THE CORNER PRESSURE OF
 -62.8.
  
 2ND REVIEW - ENGINEER RESPONDED WITH TWO STATEMENTS;
 ONE THAT THE NUMBER IS CONSERVATIVE (BUT NO
 CALCULATIONS PROVIDED) AND THAT SINCE ROOF WORK WAS
 REMOVED FROM THE PLAN, THE PRESSURE IS NOT NECESSARY.
  
 IF THE PRESSURES ARE ON THE PLAN, THEY ARE TO BE
 CORRECT.IT APPEARS THAT THE ENGINEER MAY BE USING THE
 TOTAL ZONE 3 AREA OF 16FEET (4X4) OR IS CALCULATING
 ROOF WIND PRESSURES USING MWRS.I WAS UNABLE TO LOCATE
 FBC TABLE 1609.6A WHICH THE ENGINEER REFERS TO IN HIS
 RESPONSE LETTER (THE TABLE NUMBER MAY HAVE BEEN
 MODIFIED WITH THE 2005/2006 AMENDMENTS) BUT IT APPEARS
 THAT YOU ARE REFERRING TO FBC TABLE 1609.6.2.1(1),
 SIMPLIFIED DESIGN WIND PRESSURE (MAIN
 WINDFORCE-RESISTING SYSTEM).PLEASE SEE FBC1609.2,
 DEFINITIONS, EFFECTIVE WIND AREA.FOR CLADDING
 FASTENERS, THE EFFECTIVE WIND AREA SHALL NOT BE GREATER
 THAN THE AREA THAT IS TRIBUTARY TO AN INDIVIDUAL
 FASTENER.SEE ALSO FBC TABLE 1609.6.2.1(2) NET DESIGN
 WIND PRESSURE (COMPONENT AND CLADDING), FLAT ROOF, ZONE
 3, LESS THAN 10SF, HAS A DESIGN PRESSURE OF -89.
  
 YOU MAY REMOVE THIS NUMBER, REVISE THE NUMBER, OR
 PROVIDE CALCULATIONS AS ORIGINALLY REQUESTED.
  
 12.)ADDRESSED.
  
 13.)EXTERIOR STAIRS TO COMPLY WITH ALL REQUIREMENTS
 OF FBC1022.SHOW FIRE RESISTANCE RATING FOR THE WALL
 AS WELL AS OPENINGS.
  
 2ND REVIEW, THE WINDOWS ARE ALSO REQUIRED TO BE
 PROTECTED (ONLY DOORS SHOWN AS RATED).HOWEVER, SEE
 THE EXCEPTION FBC1019.1 EXCEPTION 4, AND FBC1022.6.IF
 COMPLIANCE WITH FBC1019 CAN BE SHOWN FOR THE EXISTING
 STAIR, IT APPEARS THAT THE NEW STAIR MAY FALL UNDER THE
 EXCEPTION.
  
 14.)ADDRESSED.
  
 15-17)ADDRESSED.
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 2ND REVIEW, DISCUSSED WITH CONTRACTOR BUT NOT
 ADDRESSED.NO PLAN WAS SUBMITTED.THIS IS REQUIRED.
 ENGINEER PLEASE NOTE THAT THE PLAN WILL BE REQUIRED TO
 SHOW WHERE THE SHUTTERS WILL BE STORED AND HOW THIS
 AREA WILL BE SECURED.THIS MAY AFFECT FIRE RESISTANCE
 REQUIREMENTS SHOWN ON THE PLAN.
  
 19-23.)ADDRESSED.
  
 24.)PROVIDE A DETAIL FOR PENETRATIONS THROUGH THE
 FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES FBC7.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT FIRE RATINGS
 FOR OPENINGS ARE SHOWN.THIS COMMENT REFERS TO
 PENETRATIONS.PLEASE ADDRESS.
  
 25-26.) ADDRESSED.
  
 27.)SEE ATTACHED INSTALLATION SCHEDULE.EITHER
 COMPLETE THIS FORM OR PROVIDE ALL REQUIRED INFORMATION
 IN ANOTHER FORMAT FOR THE HURRICANE SHUTTERS.THIS
 SHOULD CORRELATE WITH A KEY PLAN SHOWING SHUTTER
 LOCATIONS.THIS APPLIES TO FIRST FLOOR WINDOWS ONLY.
 SECOND FLOOR WINDOWS ARE REQUIRED TO BE IMPACT RATED
 (WITH THE POSSIBLE EXCEPTION OF THE NEW W4 WINDOWS
 WHICH HAVE ACCESS FROM THE BALCONY).
  
 2ND REVIEW, NOT ADDRESSED.
  
 28.)EXTERIOR CHANGES TO THE PLAN WILL REQUIRE
 HISTORIC REVIEW PRIOR TO RESUBMITTAL.
  
 29-33.) ADDRESSED.
  
 NEW COMMENTS:
  
 34.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 35.)THE SMOKE ALARMS SHOWN DO NOT COMPLY WITH
 FBC907.2.10.1.2(2).NO SMOKE ALARMS SHOWN IN THE
 SLEEPING ROOMS AS REQUIRED.
  
 36.)FOR THE NON IMPACT WINDOW, CIRCLE ON THE PRODUCT
 APPROVAL WHICH GLASS OPTION YOU ARE USING AS NOT ALL
 ARE COMPLIANT FOR THE DESIGN PRESSURE REQUIRED.
  
 37.)NON IMPACT AND IMPACT FIXED WINDOW PRODUCT
 APPROVALS SUBMITTED.WHERE WILL THEY BE INSTALLED? THE
 PLAN SHOWS SINGLE HUNG ONLY ON THE ELEVATIONS, AND THE
 WINDOW SCHEDULE DOES NOT DESIGNATE TYPE OF WINDOW. ALSO
 PLEASE REVISE PLAN TO DESIGNATE WHICH WINDOWS WILL BE
 IMPACT AND WHICH WINDOWS ARE PROPOSED AS NON IMPACT (TO
 BE APPROVED BY BUILDING OFFICIAL, SEE ITEM 18).
  
 38.)SEE FBC EB 704.1, FBC903.2.7 REGARDING FIRE
 SPRINKLER REQUIREMENTS.
  
 39.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 INDICATING HOW EACH COMMENT WAS ADDRESSED.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved