Plan Review Notes For Permit 07060772 |
Permit Number |
07060772 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-27 14:11:16 | ***DENIED*** | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | EDITION. | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | 3) PROJECT IS LISTED AS MULTI-FAMILY RESIDENCE. PLEASE | | CLEARLY DEFINE NUMBER OF LIVING UNITS UNDER ROOF. SEE | | ADDRESSING FOR POSSIBLE UNIT DESIGNATIONS. | | | | 4) IF PROJECT MEETS REQUIREMENTS FOR MULTI-FAMILY, | | ADDRESS SHALL BE LOCATED ON BUILDING AND SHALL BE NOT | | LESS THAN SIX (6") IN HEIGHT AND CONTRASTING TO | | BACKGROUND. PLEASE ILLUSTRATE ON ELEVATIONS. | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED. | | | | 6) PLEASE PROVIDE LOCATION OF REQUIRED SMOKE ALARMS | | THAT SHALL BE HARD WIRED TO HOUSE ELECTRIC. ACTIVATION | | OF ONE (1) ALARM SHALL CAUSE OTHER ALARMS IN AREA TO | | ACTIVATE. | | | | 7) STAIRS TO COMPLY WITH NFPA 101, SEC. 7.2.2. | | | | 8) PLEASE PROVIDE MINIMUM INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|