Plan Review Notes
Plan Review Notes For Permit 07060772
Permit Number 07060772
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-25 10:55:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 3.)GOVERNING CODE IS TO INCLUDE 2005 AND 2006
 AMENDMENTS.
  
 4.)N/A
  
 5.)FOR ALL OF THE FIRE RATED ASSEMBLIES, SHOW
 CALCULATED FIRE RESISTANCE OR TESTED ASSEMBLY FBC 7.
  
 6.)IN THE BUILDING CODE SUMMARY ON A1, PLEASE PROVIDE
 THE TOTAL SQUARE FOOT AREA PER FLOOR, FBC TABLE 503.
  
 7.)THE PLAN SHOWS THE EXTERIOR WALLS AND 2ND FLOOR
 CEILING AS RATED.PROVIDE A SITE PLAN AND SHOW
 COMPLIANCE WITH FBC TABLE 601, FBC TABLE 602, FBC TABLE
 704.8.ARE THEY REQUIRED TO BE RATED WALLS OR ARE YOU
 EXCEEDING CODE COMPLIANCE?IT IS NOT CLEAR IF THE
 OPENINGS IN THE RATED WALLS ARE TO BE PROTECTED.
  
 8.)ROOF FELT UNDERLAYMENT FASTENING IS SPECIFIED.IT
 IS NOT CLEAR WHERE THIS WILL BE USED.EITHER REMOVE OR
 SHOW LOCATION OF WORK AND PROVIDE PRODUCT APPROVAL FOR
 THE ROOF ON A2 AND CONFIRM COMPLIANCE WITH FASTENING
 REQUIRED BY THE PRODUCT APPROVAL.
  
 9.)SHOW ALL REQUIRED FIRE RESISTANCE RATED WALLS ON
 THE FLOOR PLAN.
  
 10.)PROVIDE INFORMATION IN REGARDS TO THE TENANT
 SEPARATION WALL.SHOW REQUIRED FIRE RESISTANCE AND HOW
 THAT IS ACCOMPLISHED.NOTE THAT EXTERIOR WALLS ARE
 SHOWN AS FIRE RATED BUT THE INT BEARING WALL IS NOT,
 BUT IT APPEARS THAT THE BEARING WALL IS THE TENANT
 SEPARATION WALL AND IS REQUIRED TO HAVE A 1 HOUR RATING
 FBC708.1.AS SHOWN THE WALL DOES NOT MEET THE
 CONTINUITY REQUIREMENTS OF FBC708.4.SEE ALSO FBC EB
 703.2.
  
 11.)A1, THE ROOF IS A FLAT DECK WITH NO PARAPET WALL
 SHOWN; PROVIDE CALCULATIONS FOR THE CORNER PRESSURE OF
 -62.8.
  
 12.)THE PLAN SHOWS THAT THE LANDING AND STAIRWAY ARE
 UNDER SEPARATE PERMIT.THIS IS IN CONFLICT WITH THE
 APPLICATION WHICH STATES THAT THE STAIRS AND LANDING
 ARE WITHIN THE SCOPE OF THIS PERMIT.
  
 13.)EXTERIOR STAIRS TO COMPLY WITH ALL REQUIREMENTS
 OF FBC1022.SHOW FIRE RESISTANCE RATING FOR THE WALL
 AS WELL AS OPENINGS.
  
 14.)SHOW THAT THE DOOR FOR THE SECOND FLOOR UNIT EXIT
 DOORS MEET WIDTH REQUREMENTS OF FBC1008.8.8 (MEASURE
 FROM EACH DOOR TO THE CORNER OF STAIR/GUARDRAIL).
  
 15.)ONLY ONE HANDRAIL IS SHOWN.A HANDRAIL ON EACH
 SIDE IS REQUIRED FBC1009.11.SHOW HANDRAILS AS
 REQUIRED, WITH EXTENSIONS FBC1009.11.5.
  
 16.)SHOW DIMENSIONS OF THE SLOPED HANDRAIL EXTENSION
 AT THE BOTTOM OF THE STAIR, FBC1009.11.5 (WEST
 ELEVATION).
  
 17.)ROOF NAILING PATTERN DOES NOT COMPLY WITH FBC
 TABLE 2304.9.1 (31) FOR 10D NAILS.
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 19.)STAIR TREAD TO BE 11IN MINIMUM, FBC1009.3.
  
 20.)PROVIDE A HANDRAIL DETAIL FBC10 AND SPECIFY
 DESIGN STRENGTH FBC16.NOTE THAT THE STAIR AS DRAWN,
 WEST ELEVATION, DOES NOT MEET THE CONTINUITY
 REQUIREMENT FBC1009.11.4.
  
 21.)THE GUARD IS TO MEET THE HEIGHT REQUIREMENT OF
 FBC1012.2, INCLUDING THE GUARD AT THE STAIRS.THE
 EXTERIOR STAIRS DOES NOT FALL UNDER THE EXCEPTIONS.
 ALSO PLEASE SEE FBC1009.11.1, EXCEPTION REGARDING STAIR
 RAIL HEIGHT.
  
 22.)IT APPEARS THAT THIS IS S FOUR UNIT BUILDING, BUT
 THERE ARE ONLY TWO UNIT DESIGNATION NUMBERS (#1 AND #2,
 ON FIRST AND SECOND FLOORS).
  
 23.)A2 STATES THAT FRAMING WILL BE IN ACCORDANCE WITH
 CURRENT NDS CODE.THIS IS NOT REFERENCED IN THE FBC,
 SEE CHAPTER 35.PLEASE CHECK ALL REFERENCES ON THE
 PLAN FOR ANY WHICH MAY BE IN CONFLICT WITH FBC.
  
 24.)PROVIDE A DETAIL FOR PENETRATIONS THROUGH THE
 FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES FBC7.
  
 25.)ELEVATIONS CONFLICT AS TO TYPE OF DOOR TO BE
 INSTALLED.ONE SHOWS A GLAZED DOOR, ANOTHER SHOWS
 OPAQUE.PLANS SHOULD BE CLEAR AS TO WHAT IS PROPOSED,
 AND PRODUCT APPROVALS ARE TO BE SUBMITTED FOR ALL
 COMPONENTS AND CLADDING.
  
 26.)THE DOOR PRODUCT APPROVALS ARE FOR INSWING DOUBLE
 OPAQUE DOORS.NONE ARE SHOWN ON THE PLAN.
  
 27.)SEE ATTACHED INSTALLATION SCHEDULE.EITHER
 COMPLETE THIS FORM OR PROVIDE ALL REQUIRED INFORMATION
 IN ANOTHER FORMAT FOR THE HURRICANE SHUTTERS.THIS
 SHOULD CORRELATE WITH A KEY PLAN SHOWING SHUTTER
 LOCATIONS.THIS APPLIES TO FIRST FLOOR WINDOWS ONLY.
 SECOND FLOOR WINDOWS ARE REQUIRED TO BE IMPACT RATED
  
 28.)EXTERIOR CHANGES TO THE PLAN WILL REQUIRE
 HISTORIC REVIEW PRIOR TO RESUBMITTAL.
  
 29.)PROVIDE SLIDING GLASS DOOR PRODUCT APPROVALS.
  
 30.)DOOR SWING CONFLICTS ON A1 AND A4.IF YOU ARE
 INSTALLING INSWING DOORS, PROVIDE PRODUCT APPROVALS.
  
 31,)SHOW ALL SAFETY GLAZING REQUIREMENTS ON THE FLOOR
 PLAN OR WINDOW SCHEDULE, FBC2406.
  
 32.)THE ISSUES REGARDING THE 4X FEE FOR THIS PROPERTY
 ARE TO BE ADDRESSED PRIOR TO PERMIT ISSUANCE.
  
 33.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 INDICATING HOW EACH COMMENT WAS ADDRESSED.