Plan Review Notes For Permit 07060771 |
Permit Number |
07060771 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-27 08:36:14 | *** DENIED *** | | 1) PLANS MAY NOT BE DONE IN PEN OR PENCIL AS THEY MAY | | BE CHANGED AFTER THE FACT. | | | | 2) PLEASE SHOW CFM'S AT ALL SUPPLY AIR GRILLS. | | | | 3) COOLING LOAD CALCULATIONS ARE CALLING FOR A TOTAL | | COOLING LOAD OF 20,207 BTU'S, PLANS ARE SHOWING TWO | | SYSTEMS TOTALING 60,000 BTU'S. THE PLANS ARE CALLING | | FOR TO MUCH COOLING PLEASE CORRECT. | | | | 4) PLEASE PROVIDE RETURN AIR FOR BEDROOMS 1 AND 2, SEE | | 2004 FBC/R M1602.4. | | | | 5) PLEASE SHOW AN A/C EQUIPMENT LISTING WITH ALL | | PERTINENTINFORMATION ON THE MECHANICAL PLANS. MAKE, | | MODEL NUMBER, SEER, TOTAL AND SENSIBLE BTU'S, AND | | HEATER SIZE. | | | | 6) SHOW ON PLANS HOW RETURN AIR IS GETTING BACK TO AHU | | 1 FROM THE FAMILY ROOM. | | | | 7) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | 8) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 9) PLEASE SUBMIT TWO COPIES OF ALL PLANS AND PAPER | | WORK. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|