2008-05-20 11:00:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLANS M1.1 AND M7.1 **
 *** DENIED ***
  
 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER
 / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR
 PLENUM, SEE 2004 FBC/M 407.1.
  
 2) 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT DOES
 NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN
 PROFESSIONALS (KAMM CONSULTING) WILL BE REQUIRED TO
 PROVIDE A SHOP DRAWING REVIEW STAMP ON ANY BUILD-OUT
 PLANS THAT ARE PREPARED BY DIFFERENT DESIGNERS.
  