Plan Review Notes For Permit 07060745 |
Permit Number |
07060745 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-05-20 11:00:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | ** REVISION TO MECHANICAL PLANS M1.1 AND M7.1 ** | | *** DENIED *** | | | | 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER | | / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR | | PLENUM, SEE 2004 FBC/M 407.1. | | | | 2) 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT DOES | | NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN | | PROFESSIONALS (KAMM CONSULTING) WILL BE REQUIRED TO | | PROVIDE A SHOP DRAWING REVIEW STAMP ON ANY BUILD-OUT | | PLANS THAT ARE PREPARED BY DIFFERENT DESIGNERS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|