Plan Review Notes
Plan Review Notes For Permit 07060745
Permit Number 07060745
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-27 08:26:37DENIED;
 1. SANITARY RISER DIAGRAM VENT FOR SHOWERS TO BE
 BETWEEN THE SHOWERS ON BRANCH DRAIN AS SHOWN ON THE
 FLAT DRAWING.
 2. HORIZONTAL DRY VENTS ARE NOT PERMITED IN THE
 DRAINAGE SYSTEM. FBC PLUMBING SECTION 905.3.
 3. WATER RISER DIAGRAM; ARE ALL TOILETS TO BE ON RRW OR
 JUST THE MEN'S ROOM TOILET AND URINAL? WOMAN'S ROOM
 TOILETS ARE ON POTABLE WATER.
 4. HANDICAP SHOWERS DO NOT HAVE THE CLEAR FLOOR SPACE
 REQUIRED. THE CLEAR FLOOR SPACE SHALL EXTEND 12" PAST
 THE SEAT. WALL IS IN THE WAY. SEE FBC BUILDING CHAPTER
 11, SECTION 11-4.21.2, AND FIGURE 35A.
 PLUMBING PLAN REVIEW BY;