Plan Review Notes For Permit 07060745 |
Permit Number |
07060745 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-10-27 08:26:37 | DENIED; | | 1. SANITARY RISER DIAGRAM VENT FOR SHOWERS TO BE | | BETWEEN THE SHOWERS ON BRANCH DRAIN AS SHOWN ON THE | | FLAT DRAWING. | | 2. HORIZONTAL DRY VENTS ARE NOT PERMITED IN THE | | DRAINAGE SYSTEM. FBC PLUMBING SECTION 905.3. | | 3. WATER RISER DIAGRAM; ARE ALL TOILETS TO BE ON RRW OR | | JUST THE MEN'S ROOM TOILET AND URINAL? WOMAN'S ROOM | | TOILETS ARE ON POTABLE WATER. | | 4. HANDICAP SHOWERS DO NOT HAVE THE CLEAR FLOOR SPACE | | REQUIRED. THE CLEAR FLOOR SPACE SHALL EXTEND 12" PAST | | THE SEAT. WALL IS IN THE WAY. SEE FBC BUILDING CHAPTER | | 11, SECTION 11-4.21.2, AND FIGURE 35A. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|