Plan Review Notes
Plan Review Notes For Permit 07060745
Permit Number 07060745
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-20 12:28:14** DENIED 2ND REVIEW **
  
 *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NEW NOTE ALSO.
  
 1) NOTE: PLEASE SEE AS MENTION BY THE BASE BUILDING
 DESIGNER OF RECORD. THE NOTE ON E2.1 *SHEET NOTE #2*
 DOES MENTION THAT ALL RECEPTACLES ARE TO BE WIRED TO
 PANEL HL, YET ALL CIRCUITS FOR RECEPTACLES ON PLANS
 CALL FOR PANEL HL2. THIS IS AN ITEM WHICH COULD BE
 REDLINED HOWEVER PLANS ARE COMING BACK FOR COMMENTS
 FROM OTHER NOTES, PLEASE ADDRESS AT THIS TIME.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED TO
 COORDINATE AND SEE ADDRESSING REVIEWER FOR SUITE/UNIT
 NUMBER. IT WAS MENTIONED TO PLEASE INDICATE ON
 APPLICATION ONCE THIS WAS DETERMINED BASED ON THE
 ADDRESSING REVIEWER HOWEVER APPLICATION STILL DOES NOT
 SHOW THIS.
 THIS HAS NOT BEEN ADJUSTED IN OUR SYSTEM AND THIS
 INFORMATION WAS E-MAILED TO THE ADDRESSING REVIEW FOR
 CORRECTION AND COORDINATION.
 THE TITLE BLOCKS WERE CHANGED TO SHOW SUITE/UNIT #110.
  
 3) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW
 AND AS GONE OVER WITH BOTH DESIGNERS FROM ICE
 ENGINEERING THESE PLANS ARE BEING REQUIRED TO CONTAIN
 STAMPS FOR *SHOP DRAWING* REVIEW BY THE DESIGNERS OF
 RECORD FOR THE BASE BUILDING. PLEASE KNOW THIS IS NOT
 FOR THESE ENGINEERS TO SIGN AND SEAL PLANS, IT IS FOR
 SHOP DRAWING REVIEW STAMP WHICH WILL BE SIGNED AND
 ACKNOWLEDGES THE PLANS AND CHANGES WHICH WILL AFFECT
 THE BASE BUILDING ELECTRICAL AND OTHER SYSTEMS. THIS
 BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM UNTIL SUCH TIME A CERTIFICATE OF
 OCCUPANCY (CO) IS ISSUED. THIS INCLUDES THE
 ARCHITECTURAL AND ENGINEERING FIRMS.
 FS 471/481, FAC 61G1-16, 61G15-23
  
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS
 WAS CLEARLY STATED ON THE PREVIOUS REVIEW.
 THIS WAS CONFIRMED WITH ASSISTANT BUILDING OFFICIAL MR.
 ROBERT BROWN.
  
 ** PLEASE BE SURE COORDINATION IS MADE WITH THE BASE
 BUILDING DESIGN TEAM.
  
 4) NOTE: PLEASE SEE PANEL HL ON PLANS AND PANEL
 SCHEDULES IS STILL BEING SHOWN AS CONTAINING NO MAIN
 CIRCUIT BREAKER. THIS IS SHOWN AS MAIN LUG ONLY (MLO)
 WHEN A MAIN IS REQUIRED ON THE SECONDARY SIDE OF THE
 TRANSFORMER AS REQUIRED PER 408.36, 240.21, 240.4,
 310.16 ETC.
 PLEASE SEE THE RESPONSE LETTER MENTIONS THIS WAS
 ADDRESSED HOWEVER BASED ON PLANS SUBMITTED THIS REMAINS
 THE SAME.
 ** BASE BUILDING PLANS DO CONTAIN A MCB ON THE
 SECONDARY SIDE OF ALL TRANSFORMERS. PLEASE COORDINATE
 WITH BASE BUILDING DESIGN TEAM AND MINIMUM CODE
 REQUIREMENTS.
  
  
 5) NOTE: PLEASE PROVIDE CALCULATIONS/FIGURES ON HOW THE
 LPD WAS DERIVED.
 BASED ON SOME CALCULATIONS AND FIGURES DONE BY THIS
 OFFICE THERE IS SOME DIFFERENCES.
 PLEASE PROVIDE FRO EXAMPLE, SQ FT ON AREAS BASED ON
 SPACE BY SPACE WHICH WAS SHOWN.
 PLEASE SEE 13-415.2.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC
 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR FIRE
 ALARMS DEVICES TO BE STATED. PLEASE SEE THE LOCATIONS
 APPEAR TO MEET ADA REQUIREMENTS, HOWEVER MINIMUM LEVELS
 NEED TO BE STATED. PLEASE SEE ONLY TWO OF THE DEVICES
 ON THE NEW FA SHEET CONTAIN THE MINIMUM LEVELS NEEDED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]