2007-10-20 12:28:14 | ** DENIED 2ND REVIEW ** |
| |
| *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING. |
| PLEASE SEE NEW NOTE ALSO. |
| |
| 1) NOTE: PLEASE SEE AS MENTION BY THE BASE BUILDING |
| DESIGNER OF RECORD. THE NOTE ON E2.1 *SHEET NOTE #2* |
| DOES MENTION THAT ALL RECEPTACLES ARE TO BE WIRED TO |
| PANEL HL, YET ALL CIRCUITS FOR RECEPTACLES ON PLANS |
| CALL FOR PANEL HL2. THIS IS AN ITEM WHICH COULD BE |
| REDLINED HOWEVER PLANS ARE COMING BACK FOR COMMENTS |
| FROM OTHER NOTES, PLEASE ADDRESS AT THIS TIME. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED TO |
| COORDINATE AND SEE ADDRESSING REVIEWER FOR SUITE/UNIT |
| NUMBER. IT WAS MENTIONED TO PLEASE INDICATE ON |
| APPLICATION ONCE THIS WAS DETERMINED BASED ON THE |
| ADDRESSING REVIEWER HOWEVER APPLICATION STILL DOES NOT |
| SHOW THIS. |
| THIS HAS NOT BEEN ADJUSTED IN OUR SYSTEM AND THIS |
| INFORMATION WAS E-MAILED TO THE ADDRESSING REVIEW FOR |
| CORRECTION AND COORDINATION. |
| THE TITLE BLOCKS WERE CHANGED TO SHOW SUITE/UNIT #110. |
| |
| 3) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW |
| AND AS GONE OVER WITH BOTH DESIGNERS FROM ICE |
| ENGINEERING THESE PLANS ARE BEING REQUIRED TO CONTAIN |
| STAMPS FOR *SHOP DRAWING* REVIEW BY THE DESIGNERS OF |
| RECORD FOR THE BASE BUILDING. PLEASE KNOW THIS IS NOT |
| FOR THESE ENGINEERS TO SIGN AND SEAL PLANS, IT IS FOR |
| SHOP DRAWING REVIEW STAMP WHICH WILL BE SIGNED AND |
| ACKNOWLEDGES THE PLANS AND CHANGES WHICH WILL AFFECT |
| THE BASE BUILDING ELECTRICAL AND OTHER SYSTEMS. THIS |
| BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE |
| BUILDING DESIGN TEAM UNTIL SUCH TIME A CERTIFICATE OF |
| OCCUPANCY (CO) IS ISSUED. THIS INCLUDES THE |
| ARCHITECTURAL AND ENGINEERING FIRMS. |
| FS 471/481, FAC 61G1-16, 61G15-23 |
| |
| ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS |
| WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS |
| WAS CLEARLY STATED ON THE PREVIOUS REVIEW. |
| THIS WAS CONFIRMED WITH ASSISTANT BUILDING OFFICIAL MR. |
| ROBERT BROWN. |
| |
| ** PLEASE BE SURE COORDINATION IS MADE WITH THE BASE |
| BUILDING DESIGN TEAM. |
| |
| 4) NOTE: PLEASE SEE PANEL HL ON PLANS AND PANEL |
| SCHEDULES IS STILL BEING SHOWN AS CONTAINING NO MAIN |
| CIRCUIT BREAKER. THIS IS SHOWN AS MAIN LUG ONLY (MLO) |
| WHEN A MAIN IS REQUIRED ON THE SECONDARY SIDE OF THE |
| TRANSFORMER AS REQUIRED PER 408.36, 240.21, 240.4, |
| 310.16 ETC. |
| PLEASE SEE THE RESPONSE LETTER MENTIONS THIS WAS |
| ADDRESSED HOWEVER BASED ON PLANS SUBMITTED THIS REMAINS |
| THE SAME. |
| ** BASE BUILDING PLANS DO CONTAIN A MCB ON THE |
| SECONDARY SIDE OF ALL TRANSFORMERS. PLEASE COORDINATE |
| WITH BASE BUILDING DESIGN TEAM AND MINIMUM CODE |
| REQUIREMENTS. |
| |
| |
| 5) NOTE: PLEASE PROVIDE CALCULATIONS/FIGURES ON HOW THE |
| LPD WAS DERIVED. |
| BASED ON SOME CALCULATIONS AND FIGURES DONE BY THIS |
| OFFICE THERE IS SOME DIFFERENCES. |
| PLEASE PROVIDE FRO EXAMPLE, SQ FT ON AREAS BASED ON |
| SPACE BY SPACE WHICH WAS SHOWN. |
| PLEASE SEE 13-415.2. |
| |
| 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC |
| 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR FIRE |
| ALARMS DEVICES TO BE STATED. PLEASE SEE THE LOCATIONS |
| APPEAR TO MEET ADA REQUIREMENTS, HOWEVER MINIMUM LEVELS |
| NEED TO BE STATED. PLEASE SEE ONLY TWO OF THE DEVICES |
| ON THE NEW FA SHEET CONTAIN THE MINIMUM LEVELS NEEDED. |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |