Plan Review Notes
Plan Review Notes For Permit 07060745
Permit Number 07060745
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-03 08:20:11DENIED;
 1. MISSING REQUIRED ITEMS FROM PLANS, SEE ELECTRICAL
 PLAN REVIEW'S NOTES 1,2, AND 3.
 2. SHOW TURNING RADIUS IN THE HANDICAP STALLES ON FLOOR
 PLAN.
 3. HANDICAP URINAL NOT LISTED IN PLUMBING FIXTURE
 SCHEDULE. PLEASE LIST AN ELONGATED H/C APPROVED TYPE.
 4. PLEASE ADD NOTE ABOUT MARKING RECLAIMED WATER
 PIPING.
 5. SHOW HANDICAP SHOWERS ON FLOOR PLANS WITH SEAT,
 SHOWER HEAD ARM AND HAND RAILS.
 6. SANITARY RISER DIAGRAM IS MISSING VENT FOR THE
 SHOWERS. SEE FLAT DRAWING ON PAGE P1.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695