Plan Review Notes For Permit 07060745 |
Permit Number |
07060745 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-29 09:48:14 | *** DENIED *** | | 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER | | / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR | | PLENUM, SEE 2004 FBC/M 407.1. | | | | 2) IF THAT SPACE COULD BE USED AS A PLENUM (BUT IT'S | | NOT) THEN TEF-1 EXHAUST DUCT COULD NOT BE IN THAT | | SPACE,SEE 2004 FBC/M 601.3. | | | | 3) THE PRESSURIZED BATHROOM EXHAUST DUCT CAN NOT BE IN | | THE MECHANICAL ROOM DUE TO IT BEING AN OPEN PLENUM, SEE | | 2004 FBC/M 601.4. | | | | 4) THE BATHROOM EXHAUST DUCT ENTERING THE SHAFT IN THE | | MECHANICAL ROOM WILL NEED A FIRE AND SMOKE DAMPER, SEE | | 2004 FBC/M 607.5.5.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|