Plan Review Notes
Plan Review Notes For Permit 07060745
Permit Number 07060745
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-29 09:48:14*** DENIED ***
 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER
 / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR
 PLENUM, SEE 2004 FBC/M 407.1.
  
 2) IF THAT SPACE COULD BE USED AS A PLENUM (BUT IT'S
 NOT) THEN TEF-1 EXHAUST DUCT COULD NOT BE IN THAT
 SPACE,SEE 2004 FBC/M 601.3.
  
 3) THE PRESSURIZED BATHROOM EXHAUST DUCT CAN NOT BE IN
 THE MECHANICAL ROOM DUE TO IT BEING AN OPEN PLENUM, SEE
 2004 FBC/M 601.4.
  
 4) THE BATHROOM EXHAUST DUCT ENTERING THE SHAFT IN THE
 MECHANICAL ROOM WILL NEED A FIRE AND SMOKE DAMPER, SEE
 2004 FBC/M 607.5.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.