Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-03 11:32:17***DENIED***
  
 1) PLEASE ADVISE IF EXIT DOOR THAT IS PART OF THE ONE
 (1) HOUR WALL IS RATED.
  
 2) IN ADDITION TO THE FIRE SPRINKLER REMODEL, SEPARATE
 SHOP DRAWINGS AND PERMIT IS REQUIRED FOR FIRE ALARM
 REMODEL.
  
 3) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF RAMP WHERE
 HANDRAILS ARE REQUIRED.
  
 4) NEW FIRE/SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH UL 555 STANDARDS PRIOR TO FINAL
 INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW