Plan Review Notes
Plan Review Notes For Permit 07060745
Permit Number 07060745
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-29 17:49:40*** UNSAT ***
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. THIS WAS DONE ON
 ARCHITECTURAL SHEETS HOWEVER THE ELECTRICAL SHEETS ARE
 BLANK AT THIS LOCATION.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ALL MEP SHEETS IN ALL SETS ARE
 MISSING THE REQUIRED TITLE BLOCKS AND INFORMATION AS
 REQUIRED UNDER THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002.
 PLEASE SEE MISSING INFORMATION IS ALSO REQUIRED UNDER
 FLORIDA STATUTES 471.023.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS
 SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW
 THAT A COPY OF THE PERMIT APPLICATION HAS BEEN
 FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE
 SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE
 SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
  
 4) NOTE: PLEASE KNOW PLANS ARE BEING REVISED WHILE
 THERE IS STILL AN ACTIVE PERMIT FOR THE SHELL BUILDING.
 THE BASE SHELL BUILDING IS OF A DIFFERENT MEP DESIGN
 PROFESSIONAL AND ANY AND ALL CHANGES AND REVISIONS MADE
 TO BUILDING BY THE BUILD OUT DESIGNS AND WORK SHALL BE
 REVIEWED BY THE BASE BUILDING ENGINEER OF RECORD.
 (EXAMPLE: AS SHOP DRAWINGS)
 *** IMPORTANT**
 PLEASEALSO KNOW AS THERE ARE MANY ITEMS WHICH NOW
 AFFECT THE BASE BUILDING PLANS, COORDINATION OFNOW
 KNOWN LOADS FOR REVISED LOAD CALCULATIONS, KNOWN
 CHANGES FOR ENERGY CALCULATIONS, RISER INFORMATION,
 PANEL SCHEDULES ETC WILL ALL NEED TO BE GIVEN TO THE
 BASE BUILDING ENGINEER OF RECORD TO REVISED THE BASE
 BUILDING PLANS AND ENERGY CALCULATIONS.
 THERE ARE ITEMS WHICH WILL NOW AFFECT THIS.
 FBC 106.1.2, 106.3.5.1.2,
 NEC 408.4, 215.5, 230, 220, 240, 310 ETC.
 FBC CHAPTER 13, 13-415.1.AB.1.1, 13-415.2 ETC
  
 5) NOTE: PLEASE SEE THE PANELS AS SHOWN ON PLANS ARE
 NOT ALL SHOWN ON THE SHEETS WHERE THE PANEL SCHEDULES
 ARE LOCATED. PLEASE CLARIFY THE MCB ON THE LOAD SIDE OF
 THE TRANSFORMER AS ON BASE BUILDING PLANS.
 240.21, 408.36, 240.4, 310.16 ETC.
 FBC 106.1.2 FOR COORDINATION OF PLANS.
  
 6) NOTE: PLEASE COMPLETE AND INDICATE ALL CIRCUITING ON
 PLANS WITH PANEL SCHEDULES.
 PLEASE SEE FOR EXAMPLE SOME OF THE EXIT LIGHTS WHICH
 ARE NOTED TO BE CIRCUITED TO THE LOCAL LIGHTING CIRCUIT
 DO NOT ACTUALLY SHOW THIS. THIS IS SHOWN FOR EMERGENCY
 LIGHTS AS REQUIRED PER 700.12F BUT NOT FOR ALL EXIT
 LIGHTS.
 PLEASE COMPLETE.
 FBC 106.1.2, 106.3.5.1.2.
 NEC 408.4.
  
 7)NOTE: PLEASE SUBMIT PLANS FOR LIGHTING WHICH SHOWS
 COMPLETED INFORMATION FOR CHAPTER 13 CODE COMPLIANCE.
 PLEASE SEE SOME OF THE DEVICES ON PLANS INDICATE A NOTE
 * TO BE CHOSEN BY MANUFACTURES RECOMMENDATION*. THIS IS
 TO BE CHOSEN, DESIGNED, AND SHOWN AT THIS POINT.
 DESIGNS FOR CODE COMPLIANCE ARE NOT LEFT TO THE
 MANUFACTURE.
 PLEASE STATE DEVICE TYPES.
 PLEAS INDICATE MAXIMUM TIMES ON DEVICES CHOSEN. PLEASE
 SEE AREAS WHICH CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS AND ALSO ANY WALLS THAT EXCEED 80%.(EXAMPLE,
 PLEASE SEE THE BATHROOMS WHICH INDICATE THE ADA STALLS
 WHICH APPEAR TO HAVE WALLS AND THE DEVICES AS SHOWN MAY
 NOT PROVIDE COVERAGE INTO THESE TWO AREAS. LIGHTING
 WHICH TURNS OFF WHILE PERSONS ARE IN AREAS WHICH CREATE
 A SAFETY ISSUE SHOULD BE ADDRESSED.
 PLEASE PROVIDE REVISED ENERGY CALCULATIONS AND LIGHTING
 POWER DENSITIES AS REQUIRED. PLANS STATE THE CODE,
 WHICH IS NOT ACCEPTABLE IN LIEU OF REQUIRED DESIGNS FOR
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING SECTIONS AT A MINIMUM.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 13-415.1.AB.1.1, 13-415.2.
 ETC.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR
 MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED.
 PLEASE SEE THE LOCATIONS APPEAR TO MEET ADA
 REQUIREMENTS, HOWEVER MINIMUM LEVELS NEED TO BE
 STATED.
 IT IS KNOWN THAT THE FIRE ALARM SCOPE IS UNDER A
 SEPARATE PERMIT HOWEVER THE BASE PLANS ARE REQUIRED TO
 HAVE THE ADA COMPLIANCE SHOWN.
 ** PLEASE BE AWARE OF ANY CHANGES FROM BASE BUILDING
 AND BUILD OUT WHICH WILL NEED TO BE COORDINATED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]