Plan Review Notes For Permit 07060745 |
Permit Number |
07060745 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-02 06:55:20 | BUILDING PLAN REVIEW | | PERMIT: 07060745 | | ADD: 1641 WORTHINGTON RD | | CONT: HEDRICK BROTHERS CONST. | | TEL: (561)688-6282 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST. | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)THE SHOWER STALLS SHALL INDICATE ON THE FLOOR PLANS | | THE REQUIREMENTS OF FBC. SECTION 11-4.21. SHOW THE | | SHOWER CONTROLS IN RELATION TO THE SEAT ON THE FLOOR | | PLAN. | | | | 3)INDICATE ON THE PLANS THE TYPE OF BACKING FOR THE | | SUPPORT OF THE GRAB BARS AND SHOWER SEATS WHICH WILL | | MEET THE 250LBS REQUIREMENTS OF FBC. SEC.11-4.26. | | | | NOTE:SHEET A4.0 DETAIL #8 THERE SHALL BE SOME TYPE OF | | FIRE RESISTANT SEALANT PLACE BETWEEN THE OBJECT AND THE | | DRYWALL. INDICATE ON THE DETAIL. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|