Plan Review Notes
Plan Review Notes For Permit 07060741
Permit Number 07060741
Review Stop E
Sequence Number 4
Notes
Date Text
2007-11-01 16:23:59 
  
  
 REVISION DENIED
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SHEET E1
  
 1} THE RECEPTACLES IN THE LAUNDRY ARE CIRCUITED WITH
 THE SMALL APPLIANCE CIRCUIT IN THE BREAKFAST NOOK IN
 VIOLATION OF 210.52(B)(2).
  
 2} THE RECEPTACLE IN THE DRESSING ROOM IS ON THE BATH
 CIRCUIT IN VIOLATION OF 210.11(C)(3).
  
 3} THE SMOKE DETECTORS MUST BE ON AN AFCI CIRCUIT PER
 210.12. THEY ARE SHOWN ON A CIRCUIT THAT APPEARS TO BE
 ON A PROGRAMMABLE SWITCH CIRCUIT. PLEASE CLARIFY.
  