Plan Review Notes For Permit 07060741 |
Permit Number |
07060741 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-11-01 16:23:59 | | | | | | | REVISION DENIED | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | SHEET E1 | | | | 1} THE RECEPTACLES IN THE LAUNDRY ARE CIRCUITED WITH | | THE SMALL APPLIANCE CIRCUIT IN THE BREAKFAST NOOK IN | | VIOLATION OF 210.52(B)(2). | | | | 2} THE RECEPTACLE IN THE DRESSING ROOM IS ON THE BATH | | CIRCUIT IN VIOLATION OF 210.11(C)(3). | | | | 3} THE SMOKE DETECTORS MUST BE ON AN AFCI CIRCUIT PER | | 210.12. THEY ARE SHOWN ON A CIRCUIT THAT APPEARS TO BE | | ON A PROGRAMMABLE SWITCH CIRCUIT. PLEASE CLARIFY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|