2007-08-07 16:37:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) MECHANICAL PLANS NEED CASSIDY A/C INFORMATION IN THE
 TITLE BLOCK ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 2004 FBC, CITY WPB AMEND. 106.1.3.
  
 2) MECHANICAL PLAN SHOWS A LOOPED SUPPLY AIR DUCT AT
 THE AIR HANDLED (SEE YELLOW HIGH LIGHT) PLEASE EXPLAIN
 OR CORRECT.
  
 3) SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN SHOWING
 SUPPLY DUCTS THAT NEED TO BE SIZED.
  
 4) MECHANICAL PLAN STATES "ALL RETURN AIR THROUGH
 LOUVERED DOORS" . DOES THIS APPLY TO THE BEDROOMS AND
 THE POCKET DOOR TO THE LIVING ROOM? IF SO PLEASE STATE
 SO ON MECHANICAL PLAN IF NOT COMPLY WITH 2004 FBC/M
 601.4 BALANCED RETURN AIR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].