2007-07-30 07:35:09 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE HEAT LOAD AND A/C LOAD ARE BOTH LISTED AS
 10,000W IN THE CALCULATIONS, BUT SHOWN ON 30 AND 20 AMP
 BRAKERS ON THE PANEL SCHEDULE. SEE 220.83 FOR OPTIONAL
 EXISTING DWELLING CALCULATIONS. FIELD VERIFY THE A/C
 SYSTEM RATINGS.
  
 2} THE ICE MACHINE AT THE BAR IS ON A SMALL APPLIANCE
 CIRCUIT IN VIOLATION OF 210.52(B)(2).
  
 3} THE BREAKFAST NOOK MUST BE ON A SMALL APPLIANCE
 CIRCUIT PER 210.52(B)(1). THE LIGHTS ON CIRCUIT 28B ARE
 ALSO IN VIOLATION OF 210.52(B)(2).
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  