Plan Review Notes For Permit 07060741 |
Permit Number |
07060741 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-30 07:35:09 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE HEAT LOAD AND A/C LOAD ARE BOTH LISTED AS | | 10,000W IN THE CALCULATIONS, BUT SHOWN ON 30 AND 20 AMP | | BRAKERS ON THE PANEL SCHEDULE. SEE 220.83 FOR OPTIONAL | | EXISTING DWELLING CALCULATIONS. FIELD VERIFY THE A/C | | SYSTEM RATINGS. | | | | 2} THE ICE MACHINE AT THE BAR IS ON A SMALL APPLIANCE | | CIRCUIT IN VIOLATION OF 210.52(B)(2). | | | | 3} THE BREAKFAST NOOK MUST BE ON A SMALL APPLIANCE | | CIRCUIT PER 210.52(B)(1). THE LIGHTS ON CIRCUIT 28B ARE | | ALSO IN VIOLATION OF 210.52(B)(2). | | | | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH | | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM | | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|