2007-06-28 08:21:28 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE PROVIDE MANUFACTIRERS SPECIFICATION FOR THE
 STEAM GENERATOR TO BE INSTALLED SO THE LOAD CALCULATION
 AND LISTING CAN BE VERIFIED.
  
 2} THE KITCHEN AND BREAKFAST ROOM CIRCUITS DO NOT
 COMPLY WITH 210.52(B)(1), 20 AMP.CIRCUIT 26A MUST ALSO
 BE 20 AMP.
  
 3} THE WASHER/DRYER STACKED UNIT ARE LISTED SEPARATELY
 ON THE PANEL SCHEDULE, PLEASE CLARIFY.
  
 4} THE WHIRPOOL MUST COMPLY WITH 680.7, GFCI PROTECTED
 CIRCUIT.
  
 5} THE SMOKE ALARMS ARE ON DIFFERENT CIRCUITS
 THROUGHOUT THE RESIDENCE AND DO NOT COMPLY WITH THE
 REQUIREMENT TO INTERCONNECT, R313.1 FBC, RESIDENTIAL.
 ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  