Plan Review Notes For Permit 07060741 |
Permit Number |
07060741 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-28 08:21:28 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE PROVIDE MANUFACTIRERS SPECIFICATION FOR THE | | STEAM GENERATOR TO BE INSTALLED SO THE LOAD CALCULATION | | AND LISTING CAN BE VERIFIED. | | | | 2} THE KITCHEN AND BREAKFAST ROOM CIRCUITS DO NOT | | COMPLY WITH 210.52(B)(1), 20 AMP.CIRCUIT 26A MUST ALSO | | BE 20 AMP. | | | | 3} THE WASHER/DRYER STACKED UNIT ARE LISTED SEPARATELY | | ON THE PANEL SCHEDULE, PLEASE CLARIFY. | | | | 4} THE WHIRPOOL MUST COMPLY WITH 680.7, GFCI PROTECTED | | CIRCUIT. | | | | 5} THE SMOKE ALARMS ARE ON DIFFERENT CIRCUITS | | THROUGHOUT THE RESIDENCE AND DO NOT COMPLY WITH THE | | REQUIREMENT TO INTERCONNECT, R313.1 FBC, RESIDENTIAL. | | ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 | | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | CONFUSION IN THE FIELD. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|