Plan Review Notes For Permit 07060709 |
Permit Number |
07060709 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-27 13:32:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | FROM PREVIOUS LIST: | | | | 2.)SEE OPENING 12, DESIGN PRESSURE OF -31.8.FBC | | R301.2(2) REQUIRES A DEISGN PRESSURE OF -34.6 FOR 50SF, | | -36.7 FOR 20SF.THIS OPENING IS 45 SF.DESIGN | | PRESSURES CANNOT BE LESS THAN THE TABLE UNLESS YOU USE | | ENGINEERING.CHECK ALL OPENINGS AND REVISE ANCHORING | | AS NECESSARY. | | | | 2ND REVIEW - THE PRESSURE ON THE INSTALLATION SCHEDULE | | WAS REVISED TO -32.2, SOFTWARE WIND PRESSURES IS STILL | | -31.8.BOTH PRESSURES ARE LESS THAN FBC R TABLE | | 301.1.2.ALSO NOTE THAT THE DESIGN PRESSURE | | CALCULATIONS APPEAR TO USE THE PANEL SIZE RATHER THAN | | THE OPENING SIZE.PLEASE HAVE THE QUALIFIER CONTACT ME | | IF YOU NEED ASSISTANCE IN DETERMINING DESIGN PRESSURES. | | THIS COMMENT APPLIES TO ALL OF THE OPENINGS. | | | | |
|