Plan Review Notes
Plan Review Notes For Permit 07060709
Permit Number 07060709
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-27 13:32:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)SEE OPENING 12, DESIGN PRESSURE OF -31.8.FBC
 R301.2(2) REQUIRES A DEISGN PRESSURE OF -34.6 FOR 50SF,
 -36.7 FOR 20SF.THIS OPENING IS 45 SF.DESIGN
 PRESSURES CANNOT BE LESS THAN THE TABLE UNLESS YOU USE
 ENGINEERING.CHECK ALL OPENINGS AND REVISE ANCHORING
 AS NECESSARY.
  
 2ND REVIEW - THE PRESSURE ON THE INSTALLATION SCHEDULE
 WAS REVISED TO -32.2, SOFTWARE WIND PRESSURES IS STILL
 -31.8.BOTH PRESSURES ARE LESS THAN FBC R TABLE
 301.1.2.ALSO NOTE THAT THE DESIGN PRESSURE
 CALCULATIONS APPEAR TO USE THE PANEL SIZE RATHER THAN
 THE OPENING SIZE.PLEASE HAVE THE QUALIFIER CONTACT ME
 IF YOU NEED ASSISTANCE IN DETERMINING DESIGN PRESSURES.
 THIS COMMENT APPLIES TO ALL OF THE OPENINGS.
  
  