Plan Review Notes For Permit 07060707 |
Permit Number |
07060707 |
|
Review Stop |
P |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2009-06-18 16:57:16 | REVISION DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | NFPA 99C MED-GAS | | | | ****FROM PREVIOUS REVISION REVIEW: | | | | 1. SHT P1-103 GAS ISOMETRIC. THE MINIMUM PIPE SIZING IS | | NOT CORRECT ON SOME PIPES. 4" IS REQUIRED, (3,502 MBH @ | | 125 FEET), FROM THE METER TO THE FIRST TEE. 3" IS | | REQUIRED FOR 2,600 MBH. 2-1/2" IS REQUIRED FOR 1,300 | | MBH. 2" IS REQUIRED FOR 902 MBH, (STILL SHOWN AS 750 | | MBH). 2" IS REQUIRED FOR 750 MBH, (NO SIZE INDICATED). | | TABLE 402.4(2). | | ****RESPONSE NOTED, BUT THE REQUIREMENT FOR THE 3" PIPE | | FOR 2,600 MBH AND THE REQUIREMENT FOR THE 2-1/2" FOR | | THE 902 MBH HAS NOT BEEN ADDRESSED. | | | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | 7. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|