Plan Review Notes For Permit 07060707 |
Permit Number |
07060707 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2009-01-13 16:45:07 | ** DENIED REVIEW OF REVISIONS** | | | | ** REVISIONS SUBMITTED 12/11/2008 | | | | ELECTRICAL PLANS ARE OK HOWEVER REVIEW TO REMAIN IN | | FAILED STATUS DUE TO ENERGY CALCULATIONS. | | | | | | | | | | | | 1) NOTE: PLEASE BE SURE ALL INFORMATION REGARDING | | LIGHTING ON PLANS IS PLACED INTO THE INPUT DATA REPORT. | | REVISED CALCULATIONS WERE SUBMITTED HOWEVER INFORMATION | | ON SOME ITEMS HAS NOT YET BEEN CONFIRMED ON PLANS. | | AN EXAMPLE OF THIS IS THE LOW VOLTAGE FIXTURE *W* WHICH | | NOTES A LOW VOLTAGE REMOTE TRANSFORMER AS NEEDED. | | HOWEVER PLEASE SEE 13-415.2.ABC.1.1,.1.2 AS THE VA | | REQUIRED TO BE PART OF THE IDR IS TO BASED ON THE VA | | RATING OF THAT REMOTE TRANSFORMER. IF THESE ARE NOT YET | | LISTED THEN HOW CAN THE CALCULATIONS BE ACCURATE? | | PLEASE BE SURE TO GO OVER *ALL* FIXTURES ON PLANS AND | | BE SURE THESE ARE ALL IN THE IDR WITH THE LATEST | | REVISIONS OF FIXTURES. THIS WOULD INCLUDE LIGHTING ON | | FANS. THE FIXTURES WILL HAVE A RATING WHICH IS WHAT THE | | IDR IS REQUIRED TO SHOW. | | THE FIXTURE RATING IS THE LOAD USED NOT THE BULB | | RATING. | | | | | | |
|