2008-12-29 16:57:15 | BUILDING PLAN REVIEW |
| PERMIT: 07060707 |
| ADD: 3100 N MILITARY TRAIL |
| CONT: ANDERSON MOORE |
| TEL: (561)753-7400 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION REVIEW: REVISION# 7 / DATE 11-07-08 |
| ACTION: DENIED |
| SHEETS: A-100, A-100A, A-101 & A-103. |
| |
| 1) A-100 , A101& A-101A ALL INDICATE DOOR# 170 (D-G) AS |
| A 1 1/2 HOUR FIRE RATED DOOR BUT THE DOOR SCHEDULE ON |
| SHEET A900 INDICATE THESE DOORS TO BE INSTALLED WITH |
| DOUBLE ACTION DOOR HINGES. TABLE 302.3.2 DOES INDICATE |
| TWO HOUR WALLS ARE REQUIRED AND THE PLANS INDICATE AS |
| SUCH BUT THE DOOR OPENINGS REQUIRE OPENING PROTECTION. |
| TABLE 715.3 INDICATES THE DOOR OPENINGS TO HAVE A 1 1/2 |
| HR FIRE RATING. |
| |
| THERE ARE THREE ISUES WITH THE DOUBLE ACTION TYPE DOOR: |
| |
| 1A) SECTION 715.3.3 FIRE DOOR ASSEMBLIES SHALL ALSO |
| MEET THE THE REQUIREMENTS FOR A SMOKE AND DRAFT CONTROL |
| DOOR ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN |
| ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL BOTTOM |
| OF THE DOOR ASSEMBLY. |
| |
| 1B) 15.3.7 DOOR CLOSING. FIRE DOORS SHALL BE |
| SELF-CLOSING OR AUTOMATIC-CLOSING IN ACCORDANCE WITH |
| THIS SECTION. |
| |
| 1C)715.3.7.1 LATCH REQUIRED. UNLESS OTHERWISE |
| SPECIFICALLY PERMITTED, SINGLE FIRE DOORS AND BOTH |
| LEAVES OF PAIRS OF SIDE-HINGED SWINGING FIRE DOORS |
| SHALL BE PROVIDED WITH AN ACTIVE LATCH BOLT THAT WILL |
| SECURE THE DOOR WHEN IT IS CLOSED. |
| |
| 2) SHEET A103 DOOR OPENING # 165 B & C: |
| |
| 2A) DOOR# 165C IS INDICATED IN THE DOOR SCHEDULE AS A 1 |
| 1/2 HR RATED DOOR AND FRAME. THE DOOR SCHEDULE SHEET |
| A900 INDICATES THIS TO BE DOOR TYPE "D" PLANS DO NOT |
| INDICATE THE SIZE OF THE GLAZED WINDOW TABLE 715.4.3. |
| INDICATES FOR A 1 1/2 HR OPENING PROTECTIVE THE MAXIMUM |
| SIXE OF WIRE GLASS IS 100 SQ INCHES OR HEIGHTH 33" AND |
| WIDTH 10". PLEASE PROVIDE THIS INFORMATION ON THE |
| PLANS, DOOR SCHEDULE. |
| |
| 2B) DOOR # 165B IS A STORAGE ROOM WITHIN A STORAGE ROOM |
| , WHY DOES THIS DOOR INDICATE A FIRE RATING PLEASE SEE |
| DOOR SCHEDULE A900.ADDDITIONAL INFORMATION REQUIRED |
| 106.1.2. |
| |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |