Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-15 10:37:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING
 CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE
 HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) &
 FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS INDICATED IN THE
 DBPR WEBSITE IS 6380 SANDY HILL WAY LAKE WORTH FLA
 33463, NOT 120 S. OLIVE AVE. ETC. AS INDICATED IN THE
 TITLE BLOCK. BUSINESS LICENSE NUMBER IS 9664 AS SHOWN
 ON THE TITLE BLOCK THE CORPORATION NUMBER IS OF NO
 RELEVANCE TO THIS COMMENT.
  
 4. OK
  
 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED
 FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED
 LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT
 SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
 ****RESPONSE NOTED, BUT THE SEAL IS STILL SIGNED WITH
 WHAT APPEARS TO BE INITIALS AND NO LETTER HAS BEEN
 SUBMITTED.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS
 AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE
 INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT DETAIL R7/A302 DOES NOT REFLECT
 THE PARAPET FOR THE UPPER ROOF. SECONDARY ROOF DRAIN
 REQUIRED. (SEE DETAIL R4/A-301).
  
 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH
 DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR
 DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE
 CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND
 SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 &
 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S.
 CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 &
 1503.4.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. DETAIL
 R15 STILL DOES NOT SHOW A COLLECTOR HEAD OR
 DOWNSPOUTS.
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW
 THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE
 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO
 NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE
 CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR
 THE FAUCET, SECTION 11-4.24.7.
  
 15. OK
 16. OK
 17. OK
  
 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE SN-1 FIXTURE INCLUDING INSTALLATION
 INSTRUCTIONS. SECTION 106.1.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED. TABLE 604.3
 & 604.5, SECTION 608.2.
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
 ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO
 DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE
 SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION
 TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT
 P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE
 P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF
 BACKFLOW PER TABLE 608.1.
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPE SHOW
 THE CORRESPONDING LENGHTS AS REQUIRED. ALSO THE PIPING
 IS NOT CLEAR AT THE GB1 APPLIANCES. (DELETE BACKGROUND
 FLOOR PLAN & GAS APPLIANCES).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT SPECIFICATION 15483 IS REFERENCED AS BEING
 DESIGNED BY FBC-2001. THE ADOPTED CODE IS FBC-2004.
 PLEASE CHECK THE INFORMATION IS THE SPECIFICATION BOOKS
 AS THEY WILL BE REVIEWED COMPLETLY UPON RESUBMISSION
 AND THEY SHALL BE REQUIRED TO REFLECT THE PLANS TO BE
 APPROVED.
  
 C. OK
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE GAS PLANS WILL NOT BE
 APPROVED UNTIL THE COMMENT IS COMPLIED WITH. COMMENT
 NOT ADDRESSED.
  
 G. N/A
 H. N/A
  
 21. OK
  
 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING
 SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT
 EXITS THE BUILDING.
 ****RESPONSE NOTED, BUT P1-105 DOES NOT REFLECT THE
 RISER DIAGRAM ON SHT P1-101. PLEASE CORRELATE. SECTION
 106.1.1.
  
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
 ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS
 THEY ACCUMULATE IN THE SYSTEM.
  
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT INDICATED.
  
 36. OK
 37. OK
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE
 COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY.
  
 39. OK
  
  
 **********NEW COMMENT**********
  
 1B. INFORMATIONAL: THE CERTIFICATIONS AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF
 OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]