Date |
Text |
2008-02-15 10:37:01 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| CITY WPB MUNICIPAL CODE |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| |
| 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING |
| CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS |
| INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE |
| UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO |
| RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE |
| HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) & |
| FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS. |
| ****RESPONSE NOTED, BUT THE ADDRESS INDICATED IN THE |
| DBPR WEBSITE IS 6380 SANDY HILL WAY LAKE WORTH FLA |
| 33463, NOT 120 S. OLIVE AVE. ETC. AS INDICATED IN THE |
| TITLE BLOCK. BUSINESS LICENSE NUMBER IS 9664 AS SHOWN |
| ON THE TITLE BLOCK THE CORPORATION NUMBER IS OF NO |
| RELEVANCE TO THIS COMMENT. |
| |
| 4. OK |
| |
| 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED |
| FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN |
| USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED |
| LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT |
| SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003, |
| 61G1-16.004(5) & FS 481.2055. |
| ****RESPONSE NOTED, BUT THE SEAL IS STILL SIGNED WITH |
| WHAT APPEARS TO BE INITIALS AND NO LETTER HAS BEEN |
| SUBMITTED. |
| |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| |
| 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS |
| AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE |
| INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT DETAIL R7/A302 DOES NOT REFLECT |
| THE PARAPET FOR THE UPPER ROOF. SECONDARY ROOF DRAIN |
| REQUIRED. (SEE DETAIL R4/A-301). |
| |
| 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH |
| DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR |
| DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE |
| CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND |
| SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 & |
| 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S. |
| CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 & |
| 1503.4.3. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. DETAIL |
| R15 STILL DOES NOT SHOW A COLLECTOR HEAD OR |
| DOWNSPOUTS. |
| |
| 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH |
| SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD |
| APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET |
| DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW |
| THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE |
| 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO |
| NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE |
| CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR |
| THE FAUCET, SECTION 11-4.24.7. |
| |
| 15. OK |
| 16. OK |
| 17. OK |
| |
| 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS |
| FOR THE SN-1 FIXTURE INCLUDING INSTALLATION |
| INSTRUCTIONS. SECTION 106.1.2. |
| ****RESPONSE NOTED, COMMENT NOT ADDRESSED. TABLE 604.3 |
| & 604.5, SECTION 608.2. |
| |
| 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE |
| PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER |
| BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS. |
| SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS |
| AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES |
| NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY). |
| ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO |
| DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE |
| SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION |
| TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT |
| P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE |
| P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF |
| BACKFLOW PER TABLE 608.1. |
| |
| 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE |
| FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS |
| REVIEW: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPE SHOW |
| THE CORRESPONDING LENGHTS AS REQUIRED. ALSO THE PIPING |
| IS NOT CLEAR AT THE GB1 APPLIANCES. (DELETE BACKGROUND |
| FLOOR PLAN & GAS APPLIANCES). |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| NOTED, BUT SPECIFICATION 15483 IS REFERENCED AS BEING |
| DESIGNED BY FBC-2001. THE ADOPTED CODE IS FBC-2004. |
| PLEASE CHECK THE INFORMATION IS THE SPECIFICATION BOOKS |
| AS THEY WILL BE REVIEWED COMPLETLY UPON RESUBMISSION |
| AND THEY SHALL BE REQUIRED TO REFLECT THE PLANS TO BE |
| APPROVED. |
| |
| C. OK |
| D. OK |
| E. OK |
| |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT THE GAS PLANS WILL NOT BE |
| APPROVED UNTIL THE COMMENT IS COMPLIED WITH. COMMENT |
| NOT ADDRESSED. |
| |
| G. N/A |
| H. N/A |
| |
| 21. OK |
| |
| 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING |
| SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT |
| EXITS THE BUILDING. |
| ****RESPONSE NOTED, BUT P1-105 DOES NOT REFLECT THE |
| RISER DIAGRAM ON SHT P1-101. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 23. OK |
| 24. OK |
| 25. OK |
| 26. OK |
| |
| 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE |
| SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY |
| ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) & |
| 710.1(2). |
| ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS |
| THEY ACCUMULATE IN THE SYSTEM. |
| |
| 28. OK |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| 33. OK |
| 34. OK |
| |
| 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES & |
| INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION |
| 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105). |
| 106.3.5.1.3(7)(13). |
| ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM IS NOT INDICATED. |
| |
| 36. OK |
| 37. OK |
| |
| 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE |
| RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS |
| INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY. |
| --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK. |
| PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE |
| TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF |
| VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS. |
| SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED |
| INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS |
| REQUIRED. SECTIONS 802.3 & 802.3.2. |
| ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE |
| COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY. |
| |
| 39. OK |
| |
| |
| **********NEW COMMENT********** |
| |
| 1B. INFORMATIONAL: THE CERTIFICATIONS AND WELDING |
| PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT |
| APPLICATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF |
| OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |