Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-04 23:47:02*****DENIED*****
  
 01.ON SHEET G-001 UNDER APPLICABLE CODES, INCLUDE AS
 LIFE SAFETY CODE:NFPA 101 2003 EDITION.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.NFPA 13, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS, 2002 EDITION SHALL BE REFERENCED.
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM INSTALLATION.
  
 04.NFPA72, NATIONAL FIRE ALARM CODE, 2002 EDITION
 SHALL BE REFERENCED.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE ALARM SYSTEM INSTALLATION.
  
 05.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSIBLE.
  
 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION
 ON THE APPROPIATE EXTERIOR ELEVATION..FOR
 APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 08.FIRE DOORS AND FIRE WINDOWS TO COMPLY WITH NFPA
 80.
  
 09.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT CORRIDORS, AND OTHER
 AREAS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 10.SPECIFY THE INTERIOR FLOOR FINISHES IN TERMS OF
 CLASS I OR CLASS II.
  
 11.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING VISIBLE FROM NORTH
 MILITARY TRAIL.IT IS RECOMMENDED THAT THE FARTHER THE
 BUILDING IS FROM THE ROADSIDE, THAT ADDRESS NUMBERS BE
 LARGER THAN THE DIMENSION OF NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH (AS REQUIRED BY WEST PALM
 BEACH CODE) .IF A MONUMENT SIGN IS TO BE USED,
 ADDRESS NUMBERS SHALL BE POSTED.
  
 12.ON SHEET A-400, INDICATE FRONT AND REAR
 ELEVATIONS.
  
 13.UNABLE TO LOCATE ON SHEET A-500, THE OVERHEAD
 GARAGE DOOR(S) SHOWN ON SHEET A-400'S EAST EXTERIOR
 ELEVATION.
  
 14.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.
  
 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE
 DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK
 WILL BE REQUIRED.
  
 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM
 BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY
 IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY
 WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE
 RESCUE'S PREVENTION DIVISION.
  
 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR
 APPLICATIONS.
  
 18.PLEASE EXPLAIN THE USAGE OF THE GENERATOR, THE
 TYPE OF FUEL(S) THAT WILL BE UTILIZED, AND THE STORAGE
 OF SUCH FUEL(S) & QUANTITIES STORED.SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR ITS INSTALLATION.
  
 19.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722