2007-07-24 18:28:25 | PROJECT: 5301 SOUTH DIXIE HIGHWAY |
| |
| PROJECT DESCRIPTION: STRUCTURAL REINFORCEMENT OF |
| EXISTING STRUCTURAL FRAMING |
| |
| CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE |
| W/2006 REVISIONS |
| 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONSCITY OF |
| WEST PALM BEACH/ FLORIDA BUILDING CODE/ADMINISTRATION |
| AMENDMENTS, CHAPTER 1, 2004 EDITION |
| |
| STATUS: DENIED |
| |
| |
| COMMENTS: |
| |
| |
| 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| FOLLOWING: |
| |
| FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| |
| 2) PLEASE DESIGNATE LEVEL OF ALTERATION AS PER THE |
| FOLLOWING: |
| |
| 301.5 |
| A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| |
| 3) INDICATE OCCUPANCY AND USE: |
| |
| 301.4OCCUPANCY AND USE. |
| WHEN DETERMINING THE APPROPRIATE APPLICATION OF THE |
| REFERENCED SECTIONS OF THIS CODE, THE OCCUPANCY AND USE |
| OF A BUILDING SHALL BE DETERMINED IN ACCORDANCE WITH |
| CHAPTER 3 OF THEFLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 4) AS PER THE EXISTING BUILDING CODE, THE FOLLOWING |
| SHALL APPLY: |
| |
| 407.3.1NEW STRUCTURAL FRAME MEMBERS. |
| NEW STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF |
| DAMAGED BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, |
| SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 5) PLEASE COMPLY WITH THE FOLLOWING: |
| |
| 2101.3 CONSTRUCTION DOCUMENTS. |
| THE CONSTRUCTION DOCUMENTS SHALL SHOW ALL OF THE |
| ITEMS REQUIRED BY THIS CODE INCLUDING THE FOLLOWING: |
| 1.SPECIFIED SIZE, GRADE, TYPE AND LOCATION OF |
| REINFORCEMENT, ANCHORS AND WALL TIES. |
| |
| 6) PLEASE SUBMIT A ROOF FRAMING PLAN. INDICATE THE |
| CONTINUOUS LATERAL BRACING: |
| |
| 2319.17.2.1.8 |
| ALL TRUSSES SHALL BE PROPERLY BRACED TO ACT AS A |
| SYSTEM. SUCH BRACING SHALL BE INCLUDED AS PART OF THE |
| DESIGN DOCUMENT. |
| |
| 7)PLEASE SHOW THE BUILDING ELEVATIONS AND INDICATE |
| THE ROOF PITCH. |
| |
| 8)INDICATE SPECIES AND GRADE OF NEW STRUCTURAL LUMBER |
| TO BE USED. |
| |
| 9)PLEASE SPECIFY GRADE AND LENGTH OF ANCHOR BOLTS. |
| |
| 10) PLEASE SHOW THE DIMENSIONS OF THE EXISTING |
| FOUNDATION PADS. |
| |
| 11) PLEASE SUBMIT STRUCTURAL CALCULATIONS. |
| |
| 12) SUBMIT EPOXY SPECIFICATIONS. |
| |
| 13) PLEASE PROVIDE GROUT AND MORTAR SPECIFICATIONS. |
| |
| 14) SHOW ALL ACCESSIBILITY DIMENSIONS FOR THE BATHROOMS |
| TO BE ADDED. |
| |
| 15) THE INDICATED CONSTRUCTION VALUATION APPEARS TO BE |
| LOW. PLEASE PROVIDE SUPPORTING DATA. |
| |
| |