2007-09-19 07:13:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} ONLY ONE SERVICE IS ALLOWED PER BUILDING PER 230.2,
 2005 NEC. TWO ARE SHOWN ON THE PLAN.
  
 2} TWO PANELS ARE ON THE PLAN, ONLY ONE PANEL SCHEDULE
 IS ON THE PLAN, SEE COMMENT #1, CORRELATE THE SERVICE.
  
 3} IT APPEARS THAT ALL ELECTRIC IS EXISTING EXCEPT FOR
 THE SMOKE DETECTORS. PLEASE NOTE THE SCOPE ON THE
 PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]