2007-10-03 10:15:03 | 2004 FLORIDA BUILDING CODE WITH 2006 AMENDMENTS |
| UN-PERMITTED ADDITION TO SINGLE FAMILY DWELLING |
| CONNECTED EXISTING DETACHED GARAGE TO EXISTING DWELLING |
| AND CONVERTED TO LIVING SPACE |
| WOOD FRAME AND STUCCO CONSTRUCTION |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) THE VALUE OF THE WORK FOR THE ADDITION HAS BEEN |
| INCREASED TO $ 61515.00BASED ON ICC BUILDING |
| VALUATION DATA. ADDITIONAL PERMIT FEES AND RADON FEES |
| OF $1193.36 ARE DUE. THE PERMIT FEES ARE BASED ON THE |
| COST OF CONSTRUCTION AT THE TIME THE PERMIT WAS APPLIED |
| FOR WHICH IS $94.06 PER SQFT. |
| |
| 4) TWO SETS OF SIGNED AND SEALED PLANS ARE REQUIRED. |
| SOME OF THE DRAWINGS DO NOT HAVE THE EMBOSSED SEAL AND |
| SOME HAVE THE ENGINEER'S TITLE BLOCK BUT ARE NOT SIGNED |
| AND SEALED. |
| SEE FS 471 AND FAC 61G15-23.002. |
| |
| 5) SUBMIT ENERGY CALCULATIONS FOR THE ADDED LIVING |
| SPACE AS REQUIRED BY 2004 FBC CHAPTER 13. THE ONES THAT |
| WERE SUBMITTED ARE ON THE WRONG FORM, NEED TO BE SIGNED |
| BY THE OWNER/AGENT AND ARE NOT LEGIBLE. SEE THE |
| MECHANICAL REVIEW COMMENTS. |
| |
| 6) THE SECTION A-A ON A-1 SPECIFIES AN R-VALUE OF R-19 |
| FOR THE SINGLE ASSEMBLY CEILING. WHICH IS SHOWN WITH 2 |
| X 4 RAFTERS. R-19 INSULATION REQUIRES A MINIMUM 2 X 6 |
| ASSEMBLY. SEE FBC CHAPTER 13. |
| |
| 7) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR |
| WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL |
| HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING |
| WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT |
| EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| ADJACENT PROJECTION OR WALL. |
| EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING |
| LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE |
| PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4 |
| INCHES (102 MM). |
| PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM) |
| SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR |
| FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE |
| PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE |
| PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM |
| WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING |
| AND PARALLEL TO THE PROPERTY LINE. |
| EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND |
| SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL |
| PROTECTION BASED ON LOCATION ON THE LOT. BECAUSE THE |
| DISTANCE TO THE PROPERTY LINES IS LESS THAN 6 FEET, |
| SHOW THAT THE DISTANCE TO STRUCTURES ON ADJACENT |
| PROPERTY IS NOT LESS THAN 6 FEET. |
| |
| 8 ) SHOW COMPLIANCE WITH R403.1.4 MINIMUM FOOTING |
| DEPTH, R404.1.6 FOUNDATION HEIGHT ABOVE FINISH GRADE |
| AND R319.1(5) PROTECTION AGAINST DECAY. PROVIDE |
| DIMENSIONS FROM GRADE ON THE FOUNDATION SECTION THAT |
| SHOWS COMPLIANCE. SEE PREVIOUS COMMENTS. |
| |
| 9) SHOW COMPLIANCE WITH R301.1 DESIGN. |
| BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL |
| BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING |
| DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND |
| WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION |
| OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM |
| THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF |
| TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN |
| THROUGH THE LOAD -RESISTING ELEMENTS TO THE FOUNDATION. |
| PROVIDE DETAILS THAT SPECIFY THE CONNECTIONS USED TO |
| COMPLY. SPECIFY THE CONNECTORS AT THE ROOF RIDGE IF |
| ROOF IS FRAMED WITH RAFTERS RATHER THAN ENGINEERED |
| TRUSSES AS SHOWN ON SECTION A-A ON SHEET A-1. |
| |
| 10) PLEASE CLARIFY THE FRAMING OF THE ROOF ASSEMBLY FOR |
| THE ADDITION AND THE GARAGE. ARE THESE 2 X 4 RAFTERS AT |
| 2' O.C. OR ENGINEERED TRUSSES? IF THESE ARE 2 X 4 |
| RAFTERS WITH THE CEILING ATTACHED DIRECTLY TO THE |
| BOTTOMS OF THE RAFTERS, THE SPANS APPEAR TO BE TOO |
| MUCH. SEE FBC TABLE R802.2.3.1(2). SPECIFY THE SPANS |
| AND RAFTER LUMBER SPECIES AND GRADE. PROVIDE AN |
| ANALYSIS SHOWING THAT THE ROOF SYSTEM IS CAPABLE OF |
| WITHSTANDING THE UNIFORM AND LIVE LOADS. |
| |
| 11) THE CONNECTORS SPECIFIED FOR THE RAFTERS (SIMPSON |
| MST) DO NOT PROVIDE ANY LATERAL LOAD RESISTANCE AND |
| WITH CATHEDRAL CEILINGS THERE IS NO CEILING DIAPHRAM. |
| SPECIFY HOW THE STRUCTURE WILL RESIST THE LATERAL |
| WINDLOADS. SEE FBC R801.2 AND CITY OF WPB AMENDMENTS TO |
| FBC 106.1.2 |
| |
| 12) THE WINDOWS BESIDE THE FRONT AND REAR SWING DOORS |
| ARE REQUIRED TO BE SAFETY GLAZING PER R308.1(6). |
| |
| 13) SPECIFY THE EXTERIOR SOFFIT COVERING AT THE |
| OVERHANGS. IF SOFFIT MATERIALS ARE VINYL OR ALUMINUM |
| PRODUCT APPROVALS WILL BE REQUIRED. |
| |
| 14) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| EXTERIOR SWING DOORS, THEWINDOW MULLIONS, THE ROOF |
| COVERING MATERIAL, STORM PANELS AND ANY OTHER ITEMS |
| REGULATED BY FAC RULE 9B-72. |
| |
| 15) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| STORM PANELS. SPECIFY THE MOUNT TYPE, THE ANCHOR TYPE, |
| THE ANCHOR SPACING, EDGE DISTANCE, SPANS, ETC. |
| |
| 16)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. |
| |
| 17)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 18) THE DETACHED GARAGE THAT IS CONVERTED TO LIVING |
| SPACE IS REQUIRED TO COMPLY WITH EXISTING BUILDING CODE |
| SECTION 807.2 FOR WINDLOADS. SUBMIT 2 COPIES OF A |
| SIGNED AND SEALED WINDLOAD ANALYSIS OF THE GARAGE FROM |
| FLORIDA LICENSED ENGINEER. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |