2007-08-07 11:18:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER AS HIS INFORMATION IS IN THE TITLE BLOCK,
 SEE FAC 61G15-23.002.
  
 2) PLEASE SUBMIT ENERGY CANCULATIONS FOR THE ADDITION,
 SEE 2004 FBC 13-101.2.2.
  
 3) THE ATTIC ACCESS NEEDS TO BE WITHIN 6 FEET OF THE
 AIR HANDLER, SEE 2004 FBC/R M1305.1.3. PLEASE CORRECT.
  
 4) THE BATHROOM IN THE ADDITION NEEDS AN EXHAUST FAN,
 SEE 2004 FBC/R R303.3. PLEASE CORRECT.
  
 5) MECHANICAL PLAN SHOWS ONE 8" SUPPLY AIR DUCT FEEDING
 ONE 4" AND TWO 8" SUPPLY AIR DUCTS THIS DOES NOT SEEM
 FUNCTIONAL. PLEASE SUBMIT MANUAL D CALCULATIONS TO
 SUPPORT THE DESIGN, SEE 2004 FBC/R M1601.1.
  
 6) MECHANICAL PLAN SHOWS ONE 12" RETURN AIR DUCT TO THE
 AIR HANDLER THIS DOES NOT SEEM FUNCTIONAL. PLEASE
 SUBMIT MANUAL D CALCULATIONS TO SUPPORT THE DESIGN, SEE
 2004 FBC/R M1601.1.
  
 7) NEED TO PROVIDE FOR RETURN AIR TO BEDROOM 3 AND 4,
 SEE 2004 FBC/R M1602.4.
  
 8) PROVIDE FOR RETURN AIR FROM THE ADDITION BACK TO THE
 AIR HANDLER, SEE 2004 FBC/R M1602.4.
  