2007-06-26 07:41:09 | | | | | DENIED/INCOMPLETE INFORMATION | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | THE DESCRIPTION OF THE PROJECT IS UNCLEAR AND | | INDISCERNIBLE. THERE IS NO MENTION OF REWIRING THE | | UNIT(S). | | | | 1 } INDICATE IF THE SERVICE IS TO BE INSTALLED UNDER | | THIS PERMIT OR EXISTING. | | | | 2} THE RISER IS SHOWN WITH A METER FEEDING A PIECE OF | | EQUIPMENT, THEN TO ANOTHER METER, WHICH IS NOT ALLOWED | | PER FPL. CONSULT WITH ELECTRICAL CONTRACTOR ON THE | | PROPERLAYOUT FOR THE RISER DIAGRAM. | | | | 3) THERE IS NO 6/0 CU THW MANUFACTURED FOR ELECTRICAL | | USE AS SHOWN ON THE RISER. | | | | 4} SEE ARTICLE 250.50 FOR GEC INFORMATIION, ALSO | | 250.53(D)(1) & (2). | | | | A FULL REVIEW CANNOT BE DONE WITHOUT KNOWING THE SCOPE | | OF WORK. PLEASE INDICATE THE CODE CYCLES THIS PROJECT | | WAS DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO | | NOTES FOR CLARITY IN THE FIELD.REMOVE NOTES REGARDING | | NON PERTINENT CODES, (SEE REFERENCE TO THE SFBC, | | NOTE#2). | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|