 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE DESCRIPTION OF THE PROJECT IS UNCLEAR AND
 INDISCERNIBLE. THERE IS NO MENTION OF REWIRING THE
 UNIT(S).
  
 1 } INDICATE IF THE SERVICE IS TO BE INSTALLED UNDER
 THIS PERMIT OR EXISTING.
  
 2} THE RISER IS SHOWN WITH A METER FEEDING A PIECE OF
 EQUIPMENT, THEN TO ANOTHER METER, WHICH IS NOT ALLOWED
 PER FPL. CONSULT WITH ELECTRICAL CONTRACTOR ON THE
 PROPERLAYOUT FOR THE RISER DIAGRAM.
  
 3) THERE IS NO 6/0 CU THW MANUFACTURED FOR ELECTRICAL
 USE AS SHOWN ON THE RISER.
  
 4} SEE ARTICLE 250.50 FOR GEC INFORMATIION, ALSO
 250.53(D)(1) & (2).
  
 A FULL REVIEW CANNOT BE DONE WITHOUT KNOWING THE SCOPE
 OF WORK. PLEASE INDICATE THE CODE CYCLES THIS PROJECT
 WAS DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO
 NOTES FOR CLARITY IN THE FIELD.REMOVE NOTES REGARDING
 NON PERTINENT CODES, (SEE REFERENCE TO THE SFBC,
 NOTE#2).
  