Plan Review Notes
Plan Review Notes For Permit 07060669
Permit Number 07060669
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-12 14:16:27DENIED BY BUILDING
  
 1) THE SCOPE OF WORK IS NOT INDICATED ON THE PLANS.
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 2004 FBC AND LOCAL REQUIREMENTS. SEE FBC 106.1.1
  
 2) CLEARIFY THE PROJECT DESCRIPTION ON THE PERMIT
 APPLICATION.
  
 3) ON SHEET A1 THE CEILING INSULATION IS SPECIFIED AS
 4" THICK. THIS DOES NOT COMPLY WITH FBC CHAPTER 13.
 SPECIFY THE R- VALUE.
  
 4) ON SHEET A2 THERE ARE NO STEPS INDICATED WHERE THE
 FLOOR ELEVATIONS CHANGE FROM THE SLAB TO THE FRAME
 FLOOR. THE FOUNDATION PLAN INDICATES A 12" DIFFERENCE.
  
  
 5) ON SHEET A4 THE WRONG EDITION OF ASCE7 IS SPECIFIED.
 THE 2004 FBC REFERENCES ASCE7-02.
  
 6) ADDITIONAL COMMENTS MAY BE GENERATED WHEN THE SCOPE
 OF WORK IS CLEARIFIED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW