2007-08-01 07:30:12 | TEMP SALES 2345 OKEECHOBEE BLVD - 07060642 |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07060642 |
| ADD: 2345 OKEECHOBEE BLVD |
| CONT: POPPER & ASSOCIATES |
| TEL: (561)719-7131 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) THE PERMIT APPLICATION INDICATES THIS STRUCTURE IS |
| TO BE TEMPORARY IN NATURE. BY DEFINITION THIS IS : |
| 107.1 GENERAL.THE BUILDING OFFICIAL IS AUTHORIZED TO |
| ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY |
| USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF |
| SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN 180 |
| DAYS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT |
| EXTENSIONS FOR DEMONSTRATED CAUSE. |
| 107.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL |
| CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS |
| OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND |
| SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO |
| ENSURE THE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. |
| PLEASE HAVE THE OWNER WRITE A NOTARIZED LETTER |
| INDICATING THAT THEY ARE AWARE A TEMPORARY STRUCTURE |
| WILL BE ALLOWED FOR NO MORE THAN 180 DAYS. |
| |
| 4) PLEASE PROVIDE A SITE PLAN PROVIDING THE FOLLOWING |
| INFORMATION: AN ACCESSIBLE SITE SHALL MEET THE |
| FOLLOWING MINIMUM REQUIREMENTS: |
| (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF |
| THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE |
| PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED, |
| AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE |
| BUILDING ENTRANCE. |
| (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS, |
| ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND |
| ACCESSIBLE SPACES THAT ARE ON THE SAME SITE. |
| (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR |
| POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION |
| 11-4.4 . |
| (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN |
| ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4 |
| (5)PLEASE PROVIDE THE DISABLED PARKING AND ACCESS |
| AISLE. |
| |
| 5) SITE PLAN THAT INDICATES THE TRAILER LOCATION ALSO |
| INDICATES THE USE OF STAIRS, RAMPS AND LANDINGS PLEASE |
| PROVIDE PLANS, DETAILS & DIMENSIONS FOR HOW THIS WILL |
| BE ACCOMPLISHED. |
| A) 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE |
| SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A |
| RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM |
| RISE FOR RUN SHALL BE |
| 30" (SEE FIGURE 16). |
| B) 11-4.8.3. CLEAR WIDTH. THE MINIMUMCLEAR WIDTH |
| OF A RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART |
| OF A REQUIRED MEANS OF EGRESS SHALL NOT BELESS THAN |
| 44 INCHES WIDE. |
| C) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS |
| SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH |
| RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| CLEARENCE. |
| D) 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE |
| GREATER THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN |
| 72", THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. |
| |
| 6) FOR THE SITE BUILT STAIRS LANDINGS AND RAMP PLEASE |
| PROVIDE THE FOLLOWING DESIGN INFORMATION ON THE PLAN: |
| 2004 FL. BLDG CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF |
| |
| 7) SHEETS 1-3 OF THE GE CAPITAL MODULAR SPACE ARE |
| REVIEWED BY THE STATE. SHEET 4 NOTE 4 INDICATES THAT |
| THE MINIMUM SAFE BEARING VALUE IS TO BE 2000 PSF AND TO |
| BE VERIFIED BY THE BUILDINGS OWNER. PLEASE PROVIDE(2) |
| ORIGINAL SIGNED & SEALED SOILS REPORT.1802.2.1 |
| QUESTIONABLE SOIL. |
| WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 8) PLANS INDICATE THE USE OF 4" THICK ABS PADS OR 4X16 |
| CONCRETE PADS. FOR TEMPORARY STRUCTURES THIS BUILDING |
| IS STILL TO CONFORM TO THE FBC 107.2 CONFORMANCE. |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE THE |
| PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. THE |
| FOUNDATION SHALL BE 12" BELOW GRADE,1805.2 DEPTH OF |
| FOOTINGS. |
| THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED |
| GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE |
| APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO CONFORM TO |
| SECTIONS 1805.2.1 THROUGH 1805.2.3 . |
| |
| 9) PLEASE INDICATE IF THE DESIGN PROFESSIONAL IS GOING |
| TO PROVIDE A PERMANENT FOUNDATION AND STEM WALL OR IF |
| OTHER MATERIALS AND METHODS ARE TO BE EMPLOYED? 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 11) THE PERMIT VALUATION APPEARS TO BE CONSIDERABLY |
| LOW, IF NOT CORRECTED THE CITY WILL USE MARSHALL AND |
| SWIFT TO EVALUATE WHAT THE PERMIT FEES WILL BE. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| BUILDING PLAN REVIEW II |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |