2007-11-08 16:20:32 | |
| |
| |
| DENIED/INCOMPLETE INFORMATION |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW |
| |
| COMMENTS FROM PREVIOUS REVIEW; |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| FS, RESPECTIVELY.* NO SIGNATURES. |
| |
| 2} INDICATE THAT THE BATHROOM CIRCUITS COMPLY WITH |
| 210.11(C)(3).* STILL NOT LISTED ON THE SCHEDULE. |
| |
| 3} INDICATE WHAT THE APPLIANCE IN THE BATHROOM IS. |
| THERE IS NO SYMBOL IN THE LEGEND INDICATING VOLTAGE OR |
| AMPERAGE FOR THAT APPLIANCE. |
| |
| 4} THE PANEL SCHEDULE IS INCOMPLETE. IF PROVIDING ONE |
| IT MUST BE COMPLETE PER 106.3.5.4(8), FBC AS AMENDED. |
| |
| 6} THERE IS A CONDENSING UNIT ON THE PLAN. LOCATE THE |
| AHU IF THIS IS BEING INSTALLED UNDER THE SCOPE OF THIS |
| PERMIT. SHOW COMPLIANCE WITH 210.63 FOR THE RECEPTACLE |
| AND 110.26 FOR THE DISCONNECT. |
| |
| 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. |
| |
| NEW COMMENTS THIS REVIEW: |
| |
| 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| FOR CLARITY IN THE FIELD AND RECORD RETENTION PER |
| 106.1.3 FBC AS AMENDED. |
| |
| 2 ]SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS |
| REVIEW. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |