Plan Review Notes
Plan Review Notes For Permit 07060606
Permit Number 07060606
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-04 17:41:33DENIED
  
 THE FOLLOWING COMMENT WERE NOT ADDRESSED ON THE 1ST
 REVIEW:
  
 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ********THE PERSONS RESPONSIBLE FOR THE DRAWINGS MUST
 REVIEW AND APPROVE THE PRODUCTS TO BE USED*********
  
 8)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
 *********SUBMIT ENERGY CALCULATIONS BASED ON THE
 CONSTRUCTION OF THE ADDITION, NOTE THAT NO INSULATION
 VALUE WAS GIVEN TO THE ROOF********
  
 10)TO CONFORM TO THE ZONING (SEE ZONING REVIEW)
 **********ZONING REVIEW COMMENTS MUST BE ADDRESSED
 BEFORE PROJECT CAN BE PERMITTED*********
  
 11)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
 **********PROVIDE FULL FLOOR PLAN TO SHOW
 COMPLIANCE***********
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NEW REVIEW COMMENTS FROM PRODUCT APPROVALS:
  
 1)PRODUCT APPROVALS WERE SUBMITTED FOR BOTH SINGLE
 HUNG IMPACT WINDOWS AND FIXED NON-IMPACT, PLEASE
 PROVIDE LOCATION,TYPE AND SIZE OF WINDOWS ON THE
 DRAWINGS.
  
 2)CHOOSE A ROOFING SYSTEM FROM THE PRODUCT APPROVAL,
 NON INSULATED WOOD DECKS ARE ON PAGES 17 & 18. PLEASE
 NOTE THAT THE DESIGN PRESSURES LISTED IN THE NOA DO NOT
 MEET THE REQUIREMENTS FOR THE PERIMETER AND CORNER
 ZONES AND THEREFORE CALCULATION MUST BE PROVIDED BY AN
 ARCHITECT, ENGINEER OR ROOFING CONSULTANT. INCLUDE
 THESE CALCULATIONS WITH THE PRODUCT APPROVAL.
  
 3)THE SYMBOLS 2 & 2A ON THE FOOTING SCHEDULE SEEM TO
 BE THE OPPOSITE OF THE FOUNDATION PLAN AND WALL
 SECTIONS PLEASE CLARIFY
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved