Plan Review Notes
Plan Review Notes For Permit 07060606
Permit Number 07060606
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-22 07:46:10 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} INDICATE THAT THE BATHROOM CIRCUITS COMPLY WITH
 210.11(C)(3).
  
 3} INDICATE WHAT THE APPLIANCE IN THE BATHROOM IS.
 THERE IS NO SYMBOL IN THE LEGEND INDICATING VOLTAGE OR
 AMPERAGE FOR THAT APPLIANCE.
  
 4} THE PANEL SCHEDULE IS INCOMPLETE. IF PROVIDING ONE
 IT MUST BE COMPLETE PER 106.3.5.4(8), FBC AS AMENDED.
  
 5} INDICATE IF THE SERVICE IS NEW OR EXISTING. REMOVE
 NOTES AND SCHEMATICS THAT ARE NOT RELEVANT TO THE WORK
 TO BE PERMITTED. IF INSTALLED UNDER THIS PERMIT, PER
 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 6} THERE IS A CONDENSING UNIT ON THE PLAN. LOCATE THE
 AHU IF THIS IS BEING INSTALLED UNDER THE SCOPE OF THIS
 PERMIT. SHOW COMPLIANCE WITH 210.63 FOR THE RECEPTACLE
 AND 110.26 FOR THE DISCONNECT.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved