2007-07-11 17:57:38 | |
| |
| DENIED |
| |
| 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| ADDED TO THE PERMIT APPLICATION FEES. NOTE FEES ARE DUE |
| IN THE AMOUNT OF $ 1.44 FOR STATE OF FLORIDA RADON FEE |
| |
| 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| |
| 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL COVER |
| SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| SUBMITTED APPLICATIONS WILL BE DENIED |
| |
| 5)NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF |
| MEMBRANE, AND CONSTRUCTION STRAPS/TIES |
| |
| 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 7)ALTHOUGH THE DRAWINGS SHOW THE MINIMUM DEPTH OF |
| FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES. |
| PLEASE SEE THAT THE ELEVATION DRAWINGS ON A/2 SHOWS THE |
| FINISHED GRADE AT 36" BELOW FIN FLOOR AND THE |
| MONOLITHIC FOUNDATION IS ONLY 20" DEEP. |
| |
| 8)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| |
| 9)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| |
| 10)TO CONFORM TO THE ZONING (SEE ZONING REVIEW) |
| REGULATIONS THE ADDITION WALL THAT TIES INTO THE |
| EXISTING BUILDING ON THE SOUTH SIDE WILL BE REQUIRED TO |
| JOG OVER SO THAT THE BACK CORNER IS NOT ANY CLOSER TO |
| THE PROPERTY LINE THAN THE EXISTING BUILDING 3.43 FEET. |
| SEE THAT THE PROPOSED DISTANCE WOULD BE 3.31 THUS |
| INCREASING THE NONCONFORMITY. |
| |
| 11)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER |
| R313.1.1 FBC RES. |
| |
| 12)PROVIDE MIN ROOF SHEATHING ATTACHMENT |
| PER R803.2.3.1 FBC RES. SHALL BE 8D RING SHANK AT 6" |
| O/C EDGES AND FIELD AND 4" O/C EDGES AND FIELD IN ZONES |
| 2 & 3 |
| |
| 13)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |