2007-08-08 23:05:55 | *****DENIED***** |
| |
| |
| 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 2.THE ERECTING AND/OR INSTALLATION OF THE STRUCTURE |
| SHALL IN NO WAY INTERFERE OR HINDER EMERGENCY RESPONSE |
| ACCESS TO THE SAID PROPERTY, THE BUILDING(S), OR |
| VICINITY THEREOF (INCLUDING STREETS, FIRE LANES, ETC). |
| |
| 3.THE PROJECT ADDRESS (OR ASSIGNED ADDRESS) SHALL BE |
| IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 4.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE |
| EXTERIOR ELEVATION TO BE PLAINLY VISIBLE FROM SOUTH |
| DIXIE HIGHWAY.AS PER WEST PALM BEACH CODE, THE |
| NUMBERS SHALL BE NO LESS THAN SIX INCHES IN HEIGHT AND |
| NO LESS THAN ONE INCH IN WIDTH. |
| |
| 5.NO EMERGENCY LIGHTING AND ONLY ONE EXIT LIGHT SHOWN |
| ALTHOUGH IT APPEARS THAT THERE ARE TWO EXIT DOORS. |
| PLEASE EXPLAIN. |
| |
| 6.PROVIDE PRESCIPTIVE STRENGHT FOR STAIR |
| HANDRAILS/GUARDRAILS. |
| |
| 7.OUTSIDE STAIRS, RAMPS, AND LANDINGS SHALL BE SLIP |
| RESISTANT AND ALSO SHALL BE DESIGNED TO MINIMIZE WATER |
| ACCUMULATION ON THEIR SURFACES. |
| |
| 8.SHOW/DISPLAY THE LOCATION OF THE 2A:10BC FIRE |
| EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL |
| DISTANCE. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| ADDRESSED;PLEASE BE ADVISED THAT AS ADDITIONAL |
| INFORMATION IS RECEIVED, ADDITIONAL COMMENTS MAY APPEAR |
| THAT WERE NOT PART OF THIS REVIEW. |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |
| |
| |
| |
| |
| |
| |
| |