Plan Review Notes For Permit 07060577 |
Permit Number |
07060577 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-22 13:52:56 | *** DENIED *** | | 1) INFORMATION MISSING FROM TITLE BLOCK. | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. AS | | PLANS ARE SEALED BY AN ENGINEER. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 3) NEED SUPPLY AIR GRILL IN BEDROOM SIZED AND SHOW | | CFM'S. | | | | 4) NEED ALL RETURN AIR TRANSFER DUCT 'GRILLS' SIZED. | | | | 5) SEE A/C EQUIPMENT LISTING ON PLANS. MISSING MODEL | | NUMBERS FOR AIR HANDLER AND CONDENSER UNIT, HEATER | | SIZE, TOTAL AND SENSIBLE BTU'S. | | | | 6) SHOW LOCATION OF A/C CONDENSER UNIT ON MECHANICAL | | PLANS. | | | | 7) SHOW LOCATION OF CLOTHES DRYER VENT ON MECHANICAL | | PLANS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|