2007-06-22 13:52:56*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. AS
 PLANS ARE SEALED BY AN ENGINEER.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) NEED SUPPLY AIR GRILL IN BEDROOM SIZED AND SHOW
 CFM'S.
  
 4) NEED ALL RETURN AIR TRANSFER DUCT 'GRILLS' SIZED.
  
 5) SEE A/C EQUIPMENT LISTING ON PLANS. MISSING MODEL
 NUMBERS FOR AIR HANDLER AND CONDENSER UNIT, HEATER
 SIZE, TOTAL AND SENSIBLE BTU'S.
  
 6) SHOW LOCATION OF A/C CONDENSER UNIT ON MECHANICAL
 PLANS.
  
 7) SHOW LOCATION OF CLOTHES DRYER VENT ON MECHANICAL
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;