2007-06-22 08:54:55 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. |
| THE ENGINEER HAVING DECLARED "STRUCTURAL ONLY" ON THIS |
| SHEET, IS ASSUMED NOT RESPONSIBLE, AND SHOULD THEREFORE |
| STRIKE OR REMOVE HIS SEAL AND SIGNATURE. |
| |
| 2} } PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 3}LOCATE THE SERVICE EQUIPMENT ON THE ELECTRICAL PLAN |
| SO THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED. |
| INDICATE IF OVERHEAD OR UNDERGROUND ON THE RISER |
| DIAGRAM. |
| |
| 4} LOCATE THE A/C CONDENSER ON THE PLAN AND COMPLIANCE |
| WITH 210.63.ALSO 110.26 FOR THE DOSCONNECT. |
| |
| 5} PLEASE NOTE THAT THE DINING AREA IS REQUIRED TO BE |
| ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). THE |
| LIVING/DINING ROOMS MUST BE ON SEPERATE CIRCUITS. |
| |
| 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), SEE REVIEWED SET. |
| |
| 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) |
| AND 210.52 (A) (2), SEE FAMILY ROOM. |
| |
| 8} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| DWELLING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |