 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 THE ENGINEER HAVING DECLARED "STRUCTURAL ONLY" ON THIS
 SHEET, IS ASSUMED NOT RESPONSIBLE, AND SHOULD THEREFORE
 STRIKE OR REMOVE HIS SEAL AND SIGNATURE.
  
 2} } PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3}LOCATE THE SERVICE EQUIPMENT ON THE ELECTRICAL PLAN
 SO THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED.
 INDICATE IF OVERHEAD OR UNDERGROUND ON THE RISER
 DIAGRAM.
  
 4} LOCATE THE A/C CONDENSER ON THE PLAN AND COMPLIANCE
 WITH 210.63.ALSO 110.26 FOR THE DOSCONNECT.
  
 5} PLEASE NOTE THAT THE DINING AREA IS REQUIRED TO BE
 ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). THE
 LIVING/DINING ROOMS MUST BE ON SEPERATE CIRCUITS.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), SEE REVIEWED SET.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2), SEE FAMILY ROOM.
  
 8} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  