2008-05-02 16:18:34**SUBMITTAL DENIED**
  
 1. THE CSA EVALUATION WAS FOR THE GAS TRAIN ONLY NOT
 THE ENTIRE GENERATOR. THE CATERPILLAR GENERATOR HAS
 BEEN MODIFIED FROM THE ORIGINAL UL LISTING.
 NOTE: THE ENTIRE GENERATOR NEEDS RECERTIFICATION DUE
 TO THE FACT THE ADDED BI-FUEL SYSTEM WAS RETROFITTED.
 PLEASE PROVIDE THIS REQUIRED CERTIFICATION OF THE
 ENTIRE GENERATOR SYSTEM WITH THE ADDED RETROFITTED
 BI-FUEL SYSTEM.
  
 END OF COMMENTS:
  