Plan Review Notes
Plan Review Notes For Permit 07060548
Permit Number 07060548
Review Stop G
Sequence Number 5
Notes
Date Text
2008-02-06 11:56:10REVISION DENIED
 REFERENCE: FBC-2004 BUILDING
 NFPA-110
  
 1. LETTER DATED JANUARY 18, 2008 INDICATING THAT A
 VIBRATION HOSE CONNECTION IS NOT REQUIRED IS NOT
 APPROVED. PER NFPA 110 SECTION 7.9.3.2 APPROVED
 FLEXIBLE FUEL LINES SHALL BE USED BETWEEN THE PRIME
 MOVER AND THE FUEL PIPING. (ALSO SEE FBC-2004 SECTION
 2702.1 REQUIREMENTS FOR EMERGENCY AND STANDBY
 GERERATORS).
  
 2. THE LETTER CONCERNING THE CSA LISTING WILL BE
 RETURNED AT THIS TIME. PLEASE RESUBMIT WITH THE FIELD
 EVALUATION REPORT FOR THE AFTER MARKET ADAPTION LISTING
 FOR THE BI-FUEL FROM CSA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]