Plan Review Notes For Permit 07060548 |
Permit Number |
07060548 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2008-04-29 17:05:56 | ** DENIEDREVIEW ** | | | | 1) NOTE: PLEASE KNOW THE EVALUATION REPORT SUBMITTED BY | | POWER SECURE BY CSA INTERNATIONAL IS NOT ACCEPTABLE. | | AS STATED ON PREVIOUS REVIEW THE ENTIRE | | GENERATOR/SYSTEM NEEDS TO BE RE-LISTED. THE REPORT | | SUBMITTED SPECIFICALLY STATES THE GAS TRAIN UNIT IS THE | | ONLY ITEM WHICH WAS EVALUATED. THE REPORTS STATES THE | | GENERATOR IS UL LISTED AND HAS BEEN MODIFIED FROM THE | | ORIGINAL LISTING FROM CATERPILLAR AND NEEDS TO BE | | LISTED. THIS REVIEWER HAS CONTACTED CSA INTERNATIONAL. | | CONTACT WILL ALSO BE MADE TO PUBLIX DIRECTLY TO EXPRESS | | CONCERNS OVER LISTING. | | THE REPORT WILL BE RETAINED BY THIS OFFICE WAS REVIEWED | | BY ALL RELEVANT TRADES. | | 110.3, 90.7 | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|