2008-04-29 17:05:56** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THE EVALUATION REPORT SUBMITTED BY
 POWER SECURE BY CSA INTERNATIONAL IS NOT ACCEPTABLE.
 AS STATED ON PREVIOUS REVIEW THE ENTIRE
 GENERATOR/SYSTEM NEEDS TO BE RE-LISTED. THE REPORT
 SUBMITTED SPECIFICALLY STATES THE GAS TRAIN UNIT IS THE
 ONLY ITEM WHICH WAS EVALUATED. THE REPORTS STATES THE
 GENERATOR IS UL LISTED AND HAS BEEN MODIFIED FROM THE
 ORIGINAL LISTING FROM CATERPILLAR AND NEEDS TO BE
 LISTED. THIS REVIEWER HAS CONTACTED CSA INTERNATIONAL.
 CONTACT WILL ALSO BE MADE TO PUBLIX DIRECTLY TO EXPRESS
 CONCERNS OVER LISTING.
 THE REPORT WILL BE RETAINED BY THIS OFFICE WAS REVIEWED
 BY ALL RELEVANT TRADES.
 110.3, 90.7
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  