Date Text
2007-11-01 17:18:34DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS ARE
 NOT INDICATED ON THE ISOMETRIC FOR ALL CUT SECTIONS AS
 REQUESTED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE
 PLAN REVIEW.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD OF THE SYSTEM HAVE NOT
 BEEN INDICATED AS REQUESTED. ALL INFORMATION IS
 REQUIRED TO DO A COMPLETE PLAN REVIEW.
  
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE DISTANCE FROM THE METER
 TO THE MOST REMOTE OUTLET AS REQUESTED HAS NOT BEEN
 INDICATED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE
 PLAN REVIEW.
  
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
 ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE
 COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE
 ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE
 GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR
 RELISTING THE GENERATOR AS WELL AS THE MANUF.
 INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES.
 ******RESPONSE NOTED AND THIS CAN BE A PROVISO AS
 INDICATED IN THE ELECTRICAL PLAN REVIEW, BUT SINCE THE
 GENERATOR HAS BEEN INSTALLED ALREADY, THIS SHALL BE
 DONE AS SOON AS POSSIBLE AS TO NOT DELAY ANY
 INSPECTIONS.
  
 B. OK
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE
 REGULATORS WERE NOT SUBMITTED.
 ******NO RESPONSE, NOT ADDRESSED. WHEN SUBMITTING THE
 REGULATOR INFORMATION, INDICATE THE MODEL NUMBER AND
 THE TOTAL BTU LOAD ON EACH LOW PRESSURE SYSTEM
 DOWNSTREAM OF THE REGULATOR.
  
 D. OK
 E. OK
  
 ********NEW COMMENT********
  
 1B. OK
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]