Plan Review Notes
Plan Review Notes For Permit 07060548
Permit Number 07060548
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-31 10:23:25** PROVISO**
  
 1) NOTE: MAIN SWITCHGEAR EQUIPMENT SHALL BE VIF BY
 INSPECTOR FOR 230.76 AND 230.79. ENGINEER STATES MAIN
 CAN BE TURNED OFF BY PUSHBUTTON WITHOUT POWER.
  
 2) NOTE: GENERATOR IS TO BE RE-LISTED FROM A NATIONAL
 RECOGNIZED TESTING LABORATORY (NRTL) AS THE AFTER
 MARKET NATURAL GAS UNIT IS NOT PART OF THE LISTED
 GENERATOR FROM MANUFACTURE. THE ENGINEER'S RESPONSE IS
 THAT CSA WILL RE-LIST THE GENERATOR. THIS DOCUMENTATION
 IS TO BE SUBMITTED TO THE CITY FOR REVIEW.
 110.3, 90.7
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  