Date |
Text |
2007-10-18 14:55:53 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW:: |
| |
| A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING |
| EXISTING. |
| ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| |
| 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL |
| INDICATE MAXIMUM BTU LOAD AT 100%. |
| ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION |
| INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE |
| COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE |
| ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE |
| GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR |
| RELISTING THE GENERATOR AS WELL AS THE MANUF. |
| INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES. |
| |
| B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS |
| NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT SHT P2 WAS NOT SUBMITTED. |
| |
| C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS |
| REGULATORS. SECTION 106.1.2. |
| ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE |
| REGULATORS WERE NOT SUBMITTED. |
| |
| D. OK |
| |
| E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY |
| INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. FAC 61G15-23.002(2) & FS 471.025 ****RESPONSE |
| NOTED, BUT SHTS P1, P2 & P3 HAVE NOT BEEN SUBMITTED. |
| |
| ********NEW COMMENT******** |
| |
| 1B. SHT SD1 IS NOT SHOWN IN THE ELECTRICAL SHEET INDEX, |
| BUT SUBMITTED WITH THE ELECTRICAL SHEETS. PLEASE |
| CLARIFY. |
| |
| 2B.SHTS P1, P2 & P3 ARE INDICATED ON THE ELECTRICAL |
| SHEET INDEX, BUT NOT SUBMITTED. PLEASE CLARIFY. |
| |