Plan Review Notes
Plan Review Notes For Permit 07060548
Permit Number 07060548
Review Stop G
Sequence Number 2
Notes
Date Text
2007-10-18 14:55:53DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW::
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
 ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE
 COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE
 ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE
 GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR
 RELISTING THE GENERATOR AS WELL AS THE MANUF.
 INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES.
  
 B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHT P2 WAS NOT SUBMITTED.
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE
 REGULATORS WERE NOT SUBMITTED.
  
 D. OK
  
 E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025 ****RESPONSE
 NOTED, BUT SHTS P1, P2 & P3 HAVE NOT BEEN SUBMITTED.
  
 ********NEW COMMENT********
  
 1B. SHT SD1 IS NOT SHOWN IN THE ELECTRICAL SHEET INDEX,
 BUT SUBMITTED WITH THE ELECTRICAL SHEETS. PLEASE
 CLARIFY.
  
 2B.SHTS P1, P2 & P3 ARE INDICATED ON THE ELECTRICAL
 SHEET INDEX, BUT NOT SUBMITTED. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]