Plan Review Notes For Permit 07060548 |
Permit Number |
07060548 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-10-11 15:06:10 | ***DENIED*** | | | | THE RESPONSE LETTER IS DATED TWO (2) DAYS BEFORE THE | | FIRST FIRE PLAN REVIEW WAS COMPLETED. IT DOES NOT | | APPEAR THAT THE FIRE COMMENTS WERE CONSIDERED FOR THIS | | SUBMITTAL. PLEASE SEE THE FOLLOWING COMMENTS TAKEN | | DIRECTLY FROM THE FIRST FIRE REVIEW: | | | | 1) STATIONARY GENERATORS FOR EMERGENCY USE OR STAND BY | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | 110. | | | | 2) ABOVE GROUND FUEL TANKS SHALL BE PERMITTED TO BE | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30. NFPA | | 704 LABELS WILL BE REQUIRED. | | | | 3) SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | GENERATOR. | | | | 4) PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | 5) PROVIDE MANUFACTURE SPEC SHEETS FOR THE | | EQUIPMENT.-OK | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|