Date Text
2007-10-11 15:06:10***DENIED***
  
 THE RESPONSE LETTER IS DATED TWO (2) DAYS BEFORE THE
 FIRST FIRE PLAN REVIEW WAS COMPLETED. IT DOES NOT
 APPEAR THAT THE FIRE COMMENTS WERE CONSIDERED FOR THIS
 SUBMITTAL. PLEASE SEE THE FOLLOWING COMMENTS TAKEN
 DIRECTLY FROM THE FIRST FIRE REVIEW:
  
 1) STATIONARY GENERATORS FOR EMERGENCY USE OR STAND BY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 2) ABOVE GROUND FUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30. NFPA
 704 LABELS WILL BE REQUIRED.
  
 3) SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4) PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT
 LEAST 10' DISTANCE TO BUILDING OPENINGS.
  
 5) PROVIDE MANUFACTURE SPEC SHEETS FOR THE
 EQUIPMENT.-OK
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756