2007-10-06 14:43:41 | |
| *** DENIED2ND REVIEW *** |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| NEED TO BE ADDRESSED. |
| ** PLEASE SEE COMMENTS FROM ORIGINAL PERMIT *PROVISO* |
| ARE STILL PART OF THESE NOTES. |
| ** PLEASE SEE COMMENT WITH RESPECT TO THE GENERATOR NOW |
| BEING BI-FUEL WHICH WAS NOT PART OF THE ORIGINAL |
| GENERATOR PERMIT APPLICATION PACKAGE. |
| |
| 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. CODES |
| HAVE NOT CHANGED ON PLANS FOR NEW CODES AS APPLIED. ( |
| THIS SHOULD NOT AFFECT INSTALLATION OF ELECTRICAL). |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW #4 AND ALSO THE |
| ORIGINAL PERMIT NOTES AS PERMIT WAS ISSUED WITH A |
| *PROVISO*. THIS CONDITION OF ISSUANCE OF PERMIT WAS AT |
| CONTRACTORS OWN RISK AS THE INFORMATION SUBMITTED FOR |
| EQUIPMENT DID MEET THE CODES ARE REFLECT ON REDLINED |
| PLANS. |
| PLEASE SEE THE INFORMATION STILL SUBMITTED FOR THIS |
| PARALLEL SWITCHGEAR HAS NOT PROVED TO MEET 230.76 AND |
| 230.79. |
| 230.70, 230.71, 110.3, 90.7 ETC. |
| IT IS CLEAR THIS IS *PARALLEL SWITCH GEAR* HOWEVER THE |
| BREAKER(S) DOES NOT SHOW HOW IT MEETS THESE CODES WHEN |
| THE BREAKERS DO NOT SHOW ANY MANUAL MEANS OF DISCONNECT |
| REQUIRED FOR SERVICE MEANS OF DISCONNECT. |
| THIS IS CLEARLY THE NEW SERVICE MAIN FOR BUILDING. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 ALSO AS THE |
| ORIGINAL GENERATOR UNIT WAS DIESEL ONLY AND IS NOW A |
| BI-FUEL UNIT. |
| THE RESPONSE FROM THE ENGINEER MENTIONS TO SEE THE |
| ATTACHED LISTING FOR THE GTI FUEL SYSTEM. THE PREVIOUS |
| COMMENT WAS NOT FOR THE GTI FUEL SYSTEM. |
| THE NOTE APPLIED TO HOW THE AFTERMARKET INSTALLATION OF |
| THIS FUEL SYSTEM VOIDS THE EXISTING |
| CERTIFICATION/LISTING FROM THE GENERATOR MANUFACTURE. |
| THIS FUEL SYSTEM AND GAS CONNECTION WAS DONE WITHOUT |
| ANY PERMIT FOR INSTALLATION OF ANY OF THE GAS SYSTEMS. |
| PLEASE KNOW AS THE PERMIT WAS NEVER ISSUED FOR THE GAS |
| INSTALLATION AND THIS WORK WAS ALREADY DONE, A 4X |
| PERMIT FEE MAY STILL BE APPLIED TO THEGAS PERMIT AS |
| APPLIED FOR SUB-PERMIT. |
| ONLY ONE SUCH UNIT THIS OFFICE IS AWARE OF HAS BEEN |
| RE-LISTED BEFORE LEAVING THE FACTORY WITH THE FUEL |
| SYSTEM INSTALLED AT THE FACTORY. ALL DOCUMENTS FOR |
| RE-LISTING UNIT WOULD BE REQUIRED FOR ANY SUCH |
| PROCESS. |
| ANY AFTERMARKET PRODUCTS INSTALLED ON ANY LISTING |
| EQUIPMENT WILL REQUIRE THESE TO BE RE-LISTED/TESTED, |
| FIELD EVALUATED ETC.110.3, 90.7 ETC. (THIS WOULD ALSO |
| INCLUDE LISTING FOR POSSIBLE MECH/PLUMBING ETC). PLEASE |
| PROVIDE DOCUMENTATION FOR LISTING OF THIS LISTED |
| ASSEMBLY AS INSTALLED. |
| PLEASE HAVE THE LISTING AGENCY CONTACT THIS OFFICE IF |
| THERE ARE ANY QUESTIONS. |
| ALL WORK MUST BE DONE BY A NRTL. |
| |
| 47) NOTE:*** PLEASE KNOW THE VALUE FOR THE COMPLETE |
| SCOPE OF WORK WILL BE REQUIRED TO BE ADJUSTED AS THE |
| SCOPE OF WORK FROM ORIGINAL APPLICATION HAS GREATLY |
| INCREASED AND THE VALUE FOR ALL WORK AS SHOWN IS LOW. |
| PLEASE SEE FBC 108.3. |
| ALL LABOR, ALL MATERIALS, ALL EQUIPMENT, INSTALLAITON, |
| DESIGN COST ETC SHALL BE INCLUDED WHETHER OR NOT ANY OF |
| THESE ITEMS ARE OWNER SUPPLIED. THIS INCLUDE EQUIPMENT, |
| GENERATOR ETC. |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |