Plan Review Notes
Plan Review Notes For Permit 07060548
Permit Number 07060548
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-06 14:43:41 
 *** DENIED2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
 ** PLEASE SEE COMMENTS FROM ORIGINAL PERMIT *PROVISO*
 ARE STILL PART OF THESE NOTES.
 ** PLEASE SEE COMMENT WITH RESPECT TO THE GENERATOR NOW
 BEING BI-FUEL WHICH WAS NOT PART OF THE ORIGINAL
 GENERATOR PERMIT APPLICATION PACKAGE.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. CODES
 HAVE NOT CHANGED ON PLANS FOR NEW CODES AS APPLIED. (
 THIS SHOULD NOT AFFECT INSTALLATION OF ELECTRICAL).
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW #4 AND ALSO THE
 ORIGINAL PERMIT NOTES AS PERMIT WAS ISSUED WITH A
 *PROVISO*. THIS CONDITION OF ISSUANCE OF PERMIT WAS AT
 CONTRACTORS OWN RISK AS THE INFORMATION SUBMITTED FOR
 EQUIPMENT DID MEET THE CODES ARE REFLECT ON REDLINED
 PLANS.
 PLEASE SEE THE INFORMATION STILL SUBMITTED FOR THIS
 PARALLEL SWITCHGEAR HAS NOT PROVED TO MEET 230.76 AND
 230.79.
 230.70, 230.71, 110.3, 90.7 ETC.
 IT IS CLEAR THIS IS *PARALLEL SWITCH GEAR* HOWEVER THE
 BREAKER(S) DOES NOT SHOW HOW IT MEETS THESE CODES WHEN
 THE BREAKERS DO NOT SHOW ANY MANUAL MEANS OF DISCONNECT
 REQUIRED FOR SERVICE MEANS OF DISCONNECT.
 THIS IS CLEARLY THE NEW SERVICE MAIN FOR BUILDING.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 ALSO AS THE
 ORIGINAL GENERATOR UNIT WAS DIESEL ONLY AND IS NOW A
 BI-FUEL UNIT.
 THE RESPONSE FROM THE ENGINEER MENTIONS TO SEE THE
 ATTACHED LISTING FOR THE GTI FUEL SYSTEM. THE PREVIOUS
 COMMENT WAS NOT FOR THE GTI FUEL SYSTEM.
 THE NOTE APPLIED TO HOW THE AFTERMARKET INSTALLATION OF
 THIS FUEL SYSTEM VOIDS THE EXISTING
 CERTIFICATION/LISTING FROM THE GENERATOR MANUFACTURE.
 THIS FUEL SYSTEM AND GAS CONNECTION WAS DONE WITHOUT
 ANY PERMIT FOR INSTALLATION OF ANY OF THE GAS SYSTEMS.
 PLEASE KNOW AS THE PERMIT WAS NEVER ISSUED FOR THE GAS
 INSTALLATION AND THIS WORK WAS ALREADY DONE, A 4X
 PERMIT FEE MAY STILL BE APPLIED TO THEGAS PERMIT AS
 APPLIED FOR SUB-PERMIT.
 ONLY ONE SUCH UNIT THIS OFFICE IS AWARE OF HAS BEEN
 RE-LISTED BEFORE LEAVING THE FACTORY WITH THE FUEL
 SYSTEM INSTALLED AT THE FACTORY. ALL DOCUMENTS FOR
 RE-LISTING UNIT WOULD BE REQUIRED FOR ANY SUCH
 PROCESS.
 ANY AFTERMARKET PRODUCTS INSTALLED ON ANY LISTING
 EQUIPMENT WILL REQUIRE THESE TO BE RE-LISTED/TESTED,
 FIELD EVALUATED ETC.110.3, 90.7 ETC. (THIS WOULD ALSO
 INCLUDE LISTING FOR POSSIBLE MECH/PLUMBING ETC). PLEASE
 PROVIDE DOCUMENTATION FOR LISTING OF THIS LISTED
 ASSEMBLY AS INSTALLED.
 PLEASE HAVE THE LISTING AGENCY CONTACT THIS OFFICE IF
 THERE ARE ANY QUESTIONS.
 ALL WORK MUST BE DONE BY A NRTL.
  
 47) NOTE:*** PLEASE KNOW THE VALUE FOR THE COMPLETE
 SCOPE OF WORK WILL BE REQUIRED TO BE ADJUSTED AS THE
 SCOPE OF WORK FROM ORIGINAL APPLICATION HAS GREATLY
 INCREASED AND THE VALUE FOR ALL WORK AS SHOWN IS LOW.
 PLEASE SEE FBC 108.3.
 ALL LABOR, ALL MATERIALS, ALL EQUIPMENT, INSTALLAITON,
 DESIGN COST ETC SHALL BE INCLUDED WHETHER OR NOT ANY OF
 THESE ITEMS ARE OWNER SUPPLIED. THIS INCLUDE EQUIPMENT,
 GENERATOR ETC.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]