2007-07-16 18:51:52DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
  
 B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1.
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
  
 D. NO SITE PLANSOR SURVEYSHAS BEEN SUBMITTED
 SHOWING SET BACKS.
  
 E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025
  