2007-07-16 18:51:52 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING |
| EXISTING. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL |
| INDICATE MAXIMUM BTU LOAD AT 100%. |
| |
| B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS |
| NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS |
| REGULATORS. SECTION 106.1.2. |
| |
| D. NO SITE PLANSOR SURVEYSHAS BEEN SUBMITTED |
| SHOWING SET BACKS. |
| |
| E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY |
| INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. FAC 61G15-23.002(2) & FS 471.025 |
| |