Plan Review Notes For Permit 07060548 |
Permit Number |
07060548 |
|
Review Stop |
FUEL |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-18 16:09:01 | -------------DENIED--------------- | | | | 1. ABOVE GROUND FUEL STORAGE TANKS IN EXCESS OF 550 | | GALLONS REQUIRE APPROVAL OF THE PALM BEACH COUNTY | | DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. PLEASE | | SUBMIT 2 COPIES OF PLANS APPROVED BY PBC DERM PRIOR TO | | PERMIT ISSUANCE. FOR ADDITIONAL INFORMATION PLEASE CALL | | 561-233-2400 OR VISIT WWW.PBCGOV.COM/ERM | | | | 2. PLEASE PROVIDE SITE PLANS SHOWING THE LOCATION AND | | DISTANCE OF THE FUEL STORAGE TANK FROM PROPERTY LINES | | AND ADJACENT BUILDINGS. | | | | 3. PLAN SHOWS A DETAIL FOR INSTALLATION OF BOLLARDS, | | BUT THE PLAN DOES NOT INDICATE THE LOCATION OF THE | | BOLLARDS. PLEASE SHOW PROTECTION FROM VEHICLE DAMAGE | | PER FBC,M 303.4 | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|