Plan Review Notes
Plan Review Notes For Permit 07060548
Permit Number 07060548
Review Stop FUEL
Sequence Number 1
Notes
Date Text
2007-07-18 16:09:01-------------DENIED---------------
  
 1. ABOVE GROUND FUEL STORAGE TANKS IN EXCESS OF 550
 GALLONS REQUIRE APPROVAL OF THE PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. PLEASE
 SUBMIT 2 COPIES OF PLANS APPROVED BY PBC DERM PRIOR TO
 PERMIT ISSUANCE. FOR ADDITIONAL INFORMATION PLEASE CALL
 561-233-2400 OR VISIT WWW.PBCGOV.COM/ERM
  
 2. PLEASE PROVIDE SITE PLANS SHOWING THE LOCATION AND
 DISTANCE OF THE FUEL STORAGE TANK FROM PROPERTY LINES
 AND ADJACENT BUILDINGS.
  
 3. PLAN SHOWS A DETAIL FOR INSTALLATION OF BOLLARDS,
 BUT THE PLAN DOES NOT INDICATE THE LOCATION OF THE
 BOLLARDS. PLEASE SHOW PROTECTION FROM VEHICLE DAMAGE
 PER FBC,M 303.4
  