Plan Review Notes For Permit 07060548 |
Permit Number |
07060548 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-25 16:09:11 | *****DENIED***** | | | | | | 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | 110. | | | | 2.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA | | 704 LABELS WILL BE REQUIRED. | | | | 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | GENERATOR. | | | | 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|