Notes
Date Text
2007-07-02 10:21:22 
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THIS PERMIT IS FOR COMPLETE ION OF
 WORK STARTED UNDER PERVIOUS PERMIT THEREFORE THE NEW
 ADOPTED CODES AS OF DECEMBER 8TH, 2006 DO NOT APPLY AT
 THIS TIME.
 PLEASE SEE PLANS NEED TO CONTAIN NOTES ACCORDINGLY.
 PLEASE SUBMIT TWO COMPLETE PACKAGES OF PLANS AND SPECS.
 PLEASE SEE NO SITE PLANS/SURVEYS SHOWING ALL EQUIPMENT
 SET-BACKS ETC WERE SUBMITTED.
 FBC 106.1
  
 2) NOTE: PLEASE BE SURE ALL PLANS AND SHEETS SIGNED,
 DATED AND SEALED BY THE ENGINEER CONTAINS TITLE BLOCKS
 AS REQUIRED PER FAC 61G15-23.002.
  
 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE SPECIFIC TO
 INSTALL OF ELECTRICAL. PLANS INDICATE *AS-BUILT*
 HOWEVER STILL INDICATE EITHER/OR FOR CONDUCTORS ETC.
 PLEASE ADJUST PLANS FOR WHAT WAS INSTALLED. 310.16,
 215.5, 240.4 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE KNOW THE ORIGINAL PERMIT WAS ISSUED
 WITH CONDITIONS THAT THE EQUIPMENT INSTALLED MEETS THE
 NEC FOR SEVERAL SECTIONS. 230.70, 230.71, 230.76,
 230.79 ETC.
 THIS WAS GIVEN AS NOTES AND REDLINED ON PLANS FOR
 INSPECTOR HOWEVER THIS HAS NOT YET BEEN VERIFIED TO
 THIS DATE.
 PLEASE SEE THIS EQUIPMENT IS THE FIRST MEANS OF
 DISCONNECT AS WELL AS THE SERVICE MEANS OF DISCONNECT.
 PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT SHEETS
 FOR ALL EQUIPMENT, GENERATOR, SUB BASE FUEL TANK ETC.
 PLEASE KNOW THIS PERMIT RECORD SET OF PLANS WILL NEED
 TO BE COMPLETE WITH ALL NEW INFORMATION.
 PLEASE SUBMIT INFORMATION AS THE GENERATOR IS NOW A
 BI-FUELED UNITS. PLEASE KNOW ANY LISTINGS FOR EQUIPMENT
 WILL STILL NEED TO BE MAINTAINED FOR MANUFACTURING
 STANDARDS. ANY MODIFICATION WHICH CHANGES THE LISTING
 FOR THE MANUFACTURING OF THE GENERATOR MAY REQUIRE A
 NEW ON-SITE LISTING FORM UL OR NRTL AS RECORD. PLEASE
 KNOW AS THE EQUIPMENT FOR THE SERVICE HAS NOT BEEN
 VERIFIED WITH THIS OFFICE NO COMMENTS CAN BE MADE AT
 THIS TIME.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE NOTES AT THE EXISTING MDP1 AND
 MDP2 STATE THAT SIGNAGE WILL READ * OPTIONAL STAND-BY
 SYSTEM MAY BE PRESENT* OR WORDS TO THAT AFFECT. THIS
 WORDING WILL BE REQUIRED TO CHANGE AS THERE ARE MORE
 THAN ONE STAND-BY SYSTEMS AND SIGNS AND MAPPING OF
 THESE OTHER SYSTEMS MUST BE DETAILED AND NOTED AS BEING
 PRESENT, NOT *MAY*.
 230.2, 702.8 700.8, 701.8 ETC.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2007-07-02 10:21:15 
 PLANS REMOVED FROM INCOMING, PLANS RETURNED TO INCOMING
 WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS DONE.