2007-07-02 10:21:22 | |
| *** UNSAT *** |
| |
| |
| *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| REVIEWED AT THIS TIME. |
| |
| |
| 1) NOTE: PLEASE KNOW THIS PERMIT IS FOR COMPLETE ION OF |
| WORK STARTED UNDER PERVIOUS PERMIT THEREFORE THE NEW |
| ADOPTED CODES AS OF DECEMBER 8TH, 2006 DO NOT APPLY AT |
| THIS TIME. |
| PLEASE SEE PLANS NEED TO CONTAIN NOTES ACCORDINGLY. |
| PLEASE SUBMIT TWO COMPLETE PACKAGES OF PLANS AND SPECS. |
| PLEASE SEE NO SITE PLANS/SURVEYS SHOWING ALL EQUIPMENT |
| SET-BACKS ETC WERE SUBMITTED. |
| FBC 106.1 |
| |
| 2) NOTE: PLEASE BE SURE ALL PLANS AND SHEETS SIGNED, |
| DATED AND SEALED BY THE ENGINEER CONTAINS TITLE BLOCKS |
| AS REQUIRED PER FAC 61G15-23.002. |
| |
| 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE SPECIFIC TO |
| INSTALL OF ELECTRICAL. PLANS INDICATE *AS-BUILT* |
| HOWEVER STILL INDICATE EITHER/OR FOR CONDUCTORS ETC. |
| PLEASE ADJUST PLANS FOR WHAT WAS INSTALLED. 310.16, |
| 215.5, 240.4 ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 4) NOTE: PLEASE KNOW THE ORIGINAL PERMIT WAS ISSUED |
| WITH CONDITIONS THAT THE EQUIPMENT INSTALLED MEETS THE |
| NEC FOR SEVERAL SECTIONS. 230.70, 230.71, 230.76, |
| 230.79 ETC. |
| THIS WAS GIVEN AS NOTES AND REDLINED ON PLANS FOR |
| INSPECTOR HOWEVER THIS HAS NOT YET BEEN VERIFIED TO |
| THIS DATE. |
| PLEASE SEE THIS EQUIPMENT IS THE FIRST MEANS OF |
| DISCONNECT AS WELL AS THE SERVICE MEANS OF DISCONNECT. |
| PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT SHEETS |
| FOR ALL EQUIPMENT, GENERATOR, SUB BASE FUEL TANK ETC. |
| PLEASE KNOW THIS PERMIT RECORD SET OF PLANS WILL NEED |
| TO BE COMPLETE WITH ALL NEW INFORMATION. |
| PLEASE SUBMIT INFORMATION AS THE GENERATOR IS NOW A |
| BI-FUELED UNITS. PLEASE KNOW ANY LISTINGS FOR EQUIPMENT |
| WILL STILL NEED TO BE MAINTAINED FOR MANUFACTURING |
| STANDARDS. ANY MODIFICATION WHICH CHANGES THE LISTING |
| FOR THE MANUFACTURING OF THE GENERATOR MAY REQUIRE A |
| NEW ON-SITE LISTING FORM UL OR NRTL AS RECORD. PLEASE |
| KNOW AS THE EQUIPMENT FOR THE SERVICE HAS NOT BEEN |
| VERIFIED WITH THIS OFFICE NO COMMENTS CAN BE MADE AT |
| THIS TIME. |
| 90.7, 110.3 |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE THE NOTES AT THE EXISTING MDP1 AND |
| MDP2 STATE THAT SIGNAGE WILL READ * OPTIONAL STAND-BY |
| SYSTEM MAY BE PRESENT* OR WORDS TO THAT AFFECT. THIS |
| WORDING WILL BE REQUIRED TO CHANGE AS THERE ARE MORE |
| THAN ONE STAND-BY SYSTEMS AND SIGNS AND MAPPING OF |
| THESE OTHER SYSTEMS MUST BE DETAILED AND NOTED AS BEING |
| PRESENT, NOT *MAY*. |
| 230.2, 702.8 700.8, 701.8 ETC. |
| |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
2007-07-02 10:21:15 | |
| PLANS REMOVED FROM INCOMING, PLANS RETURNED TO INCOMING |
| WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS DONE. |