2007-07-17 17:26:23--------------DENIED-----------------
  
 1. WHAT IS THE DISTANCE BETWEEN THE PROPOSED WALL AND
 THE EXISTING CONDENSER? PLEASE VERIFY THAT CLEARANCE
 WILL BE MAINTAINED PER ITS ORIGINAL LISTING AND THAT
 MINIMUM SERVICE CLEARANCE IS MAINTAINED. FBC 106.1.1
  
 2. PLEASE SHOW GENERATOR EXHAUST DISCHARGE LOCATION TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO THE BUILDING
 SUCH AS DOORS, WINDOWS, SOFFIT VENTS AND AIR INTAKES.
  