Plan Review Notes For Permit 07060491 |
Permit Number |
07060491 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-17 17:26:23 | --------------DENIED----------------- | | | | 1. WHAT IS THE DISTANCE BETWEEN THE PROPOSED WALL AND | | THE EXISTING CONDENSER? PLEASE VERIFY THAT CLEARANCE | | WILL BE MAINTAINED PER ITS ORIGINAL LISTING AND THAT | | MINIMUM SERVICE CLEARANCE IS MAINTAINED. FBC 106.1.1 | | | | 2. PLEASE SHOW GENERATOR EXHAUST DISCHARGE LOCATION TO | | BE AT LEAST 10 FEET FROM ANY OPENINGS INTO THE BUILDING | | SUCH AS DOORS, WINDOWS, SOFFIT VENTS AND AIR INTAKES. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|