Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-26 23:03:08*****DENIED*****
  
  
 1.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 2.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 3.INCLUDE IN THE NOTES ON G-1 THAT NFPA 101, LIFE
 SAFETY CODE, 2003 EDITION SHALL BE REFERENCED.
  
 4.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
 5.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF.
  
 6.ILLUSTRATE DISTANCES TO OPENINGS AND ANY MEANS OF
 EGRESS IN REGARDS TO FUEL EXHAUST.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  